ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.15 - sign and operating device symbols
|
8.11.2.1.1(o)
|
|
|
Provide Emergency Signs ("In Case of Fire...") at all landings adjacent to all hall call fixtures
|
8/30/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.5 - Car lighting and receptacles
|
8.11.2.1.1(e) Car Lighting
|
|
|
Provide working standby (emergency) lighting inside the car when the normal power fails
|
8/30/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.3 - Lighting and receptacles
|
8.11.2.1.2(c)
|
|
|
Provide a disconnecting means that is an enclosed externally operable fused motor circuit switch or circuit breaker capable of being locked in the open position for the 110V car lights installed
|
8/30/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
Provide a written test procedure for obtaining the mechanical tripping speed for the governor per the Maintenance Control Program
|
8/30/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.15 - sign and operating device symbols
|
8.11.2.1.1(o)
|
|
|
Provide a 3-inch international symbol for emergency medical services (Star of life) on both sides of the hoistway door frame
|
8/30/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2 Design and Construction of Pits
|
|
|
Provide a clearance of not less than 0.8 inches (20 mm) for the pit ladder and the side of the car
|
8/30/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.10 - Numbering of elevators, machines, and disconnect switches
|
8.11.2.1.2(j)
|
|
|
:All disconnecting means in the machine room shall be provided with signs to identify the location of the supply side overcurrent protective devices
|
8/30/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.2-2.27.8
|
x
|
x
|
:Need to test/inspect FireFighters' Emergency Operation (FEO) RECALL, smokes, heats, shunts, hoistway venting, alarm panel,
|
4/25/2018
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.10 - Hoistway construction
|
8.11.2.1.3(p)
|
|
|
Enclose/Seal all seams/holes/penetrations in the hositway with fire-resistive construction/material
|
8/30/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Test the two-way communication means inside the car (program)
|
4/25/2018
|