Inspection
Inspection Details
Equipment ID
25305
25305
Inspection Date
8/26/2022
8/26/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Cynthia "CJ" Brady
Cynthia "CJ" Brady
Mechanic Name
Scott Breihan
Scott Breihan
Relief Valve Pressure
525
525
Slide
Governor Rope Pull
Door Closing Force
15F/10R
15F/10R
External ID
c65a9428-f967-4658-89b5-746c96e33760
c65a9428-f967-4658-89b5-746c96e33760
Location
Kirkwood Performing Arts Ctr
210 E Monroe Ave, Kirkwood, MO
Phone: (000) 000-0000
210 E Monroe Ave, Kirkwood, MO
Phone: (000) 000-0000
Owner
Attn: Trace A. Walls
Kirkwood Performing Arts Ctr
210 E Monroe Ave, Kirkwood, MO 63122
Phone: (814) 984-5947
Email: Wallsta@kirkwoodmo.org
Kirkwood Performing Arts Ctr
210 E Monroe Ave, Kirkwood, MO 63122
Phone: (814) 984-5947
Email: Wallsta@kirkwoodmo.org
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 11/8/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) | No | No | Written evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site. | 11/8/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Install a code date plate. It shall read A17.1-2016 | 11/8/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | The disconnect located in the machine room shall be provided with a sign to identify the location of the supply side overcurrent protective device. | 11/8/2022 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | A monthly record of findings for firefighters' service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be available on-site. | 11/8/2022 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | When testing Phase 2 fire service, the mezzanine floor was not over-ridden. | 8/26/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO state operating certificate and a state identification sticker shall be posted. | 11/8/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The annual inspection was not finished. The following testing items shall be completed: Relief pressure, emergency light, emergency bell, emergency phone, pressure switch, and low oil timer. | 8/26/2022 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Fire service is not operating properly. The 2nd floor key switch is not overridden when fire service is activated. | 10/28/2022 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | No | No | Compliant/required documentation & MCP shall be kept in equipment room (neat/organized and not on car top) including wiring diagrams, oil log, and fire service log, recorded monthly. MCP and logs are not being documented properly. | 2/14/2024 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Two-way communication device shall give proper location message. Agent said no location message is being given. | 3/26/2024 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. | 4/16/2024 |
| A17.1-2016 : Elevators | 2.11 - Disconnecting Means and Control | 2.26.4.1 | Yes | No | The mechanic turned off the disconnect, then turned it back on, but the controller would not turn back on. Investigate the source of problem and take corrective action. | 9/11/2024 |
| A17.1-2016 : Elevators | 2.4 - Machine space | 8.6.4.8 Machine Room and Machinery Space | No | No | Top floor is a machien space that requires 19 foot candles of lighting in fron of door jam. | 12/19/2025 |
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Up to date operating certificate required in the elevator machine room. | 12/19/2025 |
| A17.1-2016 : Elevators | 2.4 - Machine space | 8.10.2.2.2(i) | No | No | Top floor is a machine space and requires 19ft candles of lighting in front of door jam | |
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Up to date operating certificate required in elevator, cab or near elevator equipment | 8/24/2026 |