Inspection
Inspection Details
Equipment ID
168
168
Inspection Date
9/14/2017
9/14/2017
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Kurt Zimmerman
Kurt Zimmerman
Mechanic Name
Relief Valve Pressure
Slide
Governor Rope Pull
Door Closing Force
23
23
External ID
Location
Emerson Corporate Office
8000 W Florissant Rd, Ferguson, MO
Phone: (314) 553-2229
8000 W Florissant Rd, Ferguson, MO
Phone: (314) 553-2229
Owner
Emerson Electric
8000 W Florissant Rd, Ferguson, MO 63136
8000 W Florissant Rd, Ferguson, MO 63136
Billing
Attn: DCM Group
8300 Eager Rd, Ste 601, , MO 63144
8300 Eager Rd, Ste 601, , MO 63144
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Clean oil & dirt from elevator car top | 12/3/2025 |
| MO Minimum : Elevators | (A) - Hoistways | (A)13 | No | No | A temporary construction barrier was installed in the elevator hoistway between the elevator cars. This barrier is designed for only temporary use and shall be removed from the hoistway. | 12/3/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Clean oil & dirt from elevator car top. | 12/3/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The emergency car lighting is not operational, likely indicating that the back-up power device (battery) has failed. The fixture shall be repaired to operate. Reinspection required. | 3/27/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | There is not “In Case of Fire” signage at each landing as required by the building code. | 12/3/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Category 5 incomplete, lower and hold 125%, unintended motion full load down, car and counterweight buffers need smashed, safeties shall be set with 100% capacity, and slide shall be recorded in order to complete category 5 testing. | 12/3/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.1 Making Safety Devices Inoperative or Ineffective (Re-Inspection) | Yes | No | Governor is improperly functioning deeming the unit unsafe to operate, or ride until proper repairs are made. | 2/22/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Incomplete test. Both buffers shall be struck, safeties shall be set with full capacity, and slide shall be recorded. | 2/22/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | Car top light is inoperable. Means shall be provided in order for the car top light to properly function. | 2/22/2026 |