Inspection
Inspection Details
Equipment ID
8772
8772
Inspection Date
9/20/2022
9/20/2022
Inspection Type
Reinspection
Reinspection
Inspector Name
Michial Linenfelser
Michial Linenfelser
Mechanic Name
James DeBell
James DeBell
Relief Valve Pressure
450
450
Slide
Governor Rope Pull
Door Closing Force
22
22
External ID
4478f49f-6c78-46f8-aefb-8c0affce7a2e
4478f49f-6c78-46f8-aefb-8c0affce7a2e
Location
NPIF2 13600 Shoreline Dr LLC
13600 Shoreline Dr, Earth City, MO
Phone: (816) 888-7873
13600 Shoreline Dr, Earth City, MO
Phone: (816) 888-7873
Owner
Attn: NPIF2 13600 Shoreline Dr LLC
NPIF2 13600 Shoreline Dr LLC
4825 NW 41st St, Ste 500, Riverside, MO 64150
Phone: (816) 888-7380
Email: JWright@northpointkc.com
NPIF2 13600 Shoreline Dr LLC
4825 NW 41st St, Ste 500, Riverside, MO 64150
Phone: (816) 888-7380
Email: JWright@northpointkc.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone shall work. 1.6 | 7/13/2020 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) | Yes | No | OSV is not sealed and needs full load test and tripping speed checked. Re-inspection required | 9/20/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | A copy of the MCP shall be kept in the machine room for each elevator | 1/30/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | A copy of the MCP shall be kept in the machine room for each elevator. | 1/30/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 1/30/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Fire extinguisher in machine room is expired. Replace or have serviced | 1/30/2024 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Battery lowering device is not working. Re-inspection is required | 1/18/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | A written copy of the MCP shall be kept in the machine room for each unit | 1/30/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 1/30/2024 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone shall work | 12/11/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Current Fire Extinguisher is expired and shall be replaced with a valid fire extinguisher. | 7/30/2026 |