Inspection
Inspection Details
Equipment ID
8141
8141
Inspection Date
8/16/2018
8/16/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Rick Buttice
Rick Buttice
Mechanic Name
Robert Kehm
Robert Kehm
Relief Valve Pressure
Slide
Governor Rope Pull
N/A
N/A
Door Closing Force
18
18
External ID
5e81af4b-82e2-4de4-9604-d0facc89e671
5e81af4b-82e2-4de4-9604-d0facc89e671
Location
St. Louis Police Department
1915 OLIVE ST, SAINT LOUIS, MO
1915 OLIVE ST, SAINT LOUIS, MO
Owner
St. Louis City of- Police Dept
1200 CLARK AVE, SAINT LOUIS, MO 63103-2801
1200 CLARK AVE, SAINT LOUIS, MO 63103-2801
Billing
Attn: St. Louis Metro Police Dept Bldgs Division
1200 CLARK AVE, SAINT LOUIS, MO 63103-2801
1200 CLARK AVE, SAINT LOUIS, MO 63103-2801
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 8/24/2020 | ||
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Operation of elevators equipped with standby or emergency power shall be tested to determine conformance with the applicable requirements. | 8/11/2020 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 8/16/2021 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | The fire extinguisher is expired. | 12/27/2023 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | x | The emergency phone is not working. It dials out, but no one answers. | 11/20/2023 | |
| A17.1-2016 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 8.6.4.11 Runby (Re-Inspect) | x | x | Ropes shall be shortened to allow activation of top final before full counterweight buffer compression, resulting in loss of traction. Elevator Red Tagged. | 8/6/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | x | Detector edge shall work with cab lighting off. Door safety circuit cannot be wired to a lighting circuit. | 8/6/2024 | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | Machine room door shall be self-closing and self-locking. | 9/25/2025 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | COP shall have car number displayed (multiple units onsite). | 9/25/2025 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | Detector edge shall work with cab lighting off. Door safety circuit cannot be wired to a lighting circuit. Note: Elevator is about to undergo modernization and violation to be corrected at that time. | 9/25/2025 | ||
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Emergency power needs to be tested. | 9/25/2025 |