Inspection
Inspection Details
Equipment ID
2133
2133
Inspection Date
9/16/2022
9/16/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Gallaher
Michael Gallaher
Mechanic Name
Jonathan Harrison
Jonathan Harrison
Relief Valve Pressure
450
450
Slide
Governor Rope Pull
Door Closing Force
25
25
External ID
724c6e20-eac6-49ac-a064-00a759e3b52d
724c6e20-eac6-49ac-a064-00a759e3b52d
Location
Marcler C Shepard I
2801 Martin Luther King Dr, St. Louis, MO
Phone: (314) 535-8976
2801 Martin Luther King Dr, St. Louis, MO
Phone: (314) 535-8976
Owner
Attn: Fulson Housing Group
Fulson Housing Group
250 NE Mulberry St, Lee's Summit, MO 64086
Phone: (000) 000-0000
Fulson Housing Group
250 NE Mulberry St, Lee's Summit, MO 64086
Phone: (000) 000-0000
Billing
Attn: Fulson Housing Group
Fulson Housing Group
220 NW Executive Way, Lee's Summit, MO 64063
Phone: (000) 000-0000
Email: shepard1@fulsonhousing.com
Fulson Housing Group
220 NW Executive Way, Lee's Summit, MO 64063
Phone: (000) 000-0000
Email: shepard1@fulsonhousing.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 2.1 - Access to machine space | 1001.2(b)(1) | The elevator machine room door shall be self-closing/self-locking and shall be operable from the interior space without the use of a key. | 9/25/2020 | ||
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1001.2(b)(7) | There is no fire extinguisher in the machine room, as required. Provide an ABC type extinguisher of proper size for the room. | 9/25/2020 | ||
| A17.1-1996 : Elevators | 2.11 - Disconnecting Means and Control | 210.4 | A major alteration was performed alteration was performed on this elevator in 2005. At the time of the alteration, the adopted code was A17.1 1996 which required that the elevator be brought up to A17.3 and A17.1 1996. This requires that a 110 volt disconnect be installed in the elevator machine room to remove power to the elevator cab lights. There is no 110 volt disconnect in the machine room. Install a 110 volt disconnect for the elevator cab lights that meet or exceed the A17.1 1996 requirements. | 9/25/2020 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | x | Provide existing phone to work with 24/7 support | 9/22/2021 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | x | Provide existing emergency lights and bell to work | 9/22/2021 | |
| MO Minimum : Elevators | (A) - Hoistways | (A)6 | First floor door interlock (hoistway) missing cover, replace as needed | 11/17/2022 | ||
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Provide existing phone to work with 24/7 support | 9/22/2021 | |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Provide existing emergency lights and bell to work | 9/22/2021 | |
| A17.1-1996 : Elevators | 3.17 - Door and gate equipment | 1001.2(c)(23) | First floor door lock (hoistway) missing cover | 11/17/2022 | ||
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A copy of the current state operating certificate shall be on display in the machine room | 10/3/2022 | ||
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | Lighting in car shall have 2 bulbs. Ceiling panels in car are open egg crate type, providing no protection for passengers in event of bulb breakage, replace with solid type panels or install plastic tubes and end caps on bulbs | 10/3/2022 | ||
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | place current operating certificate in machine room | 9/13/2023 | ||
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | Provide machine room door to be self closing. | 11/19/2024 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | Cylinder packing is worn and leaking, repair as needed. | 11/19/2024 | ||
| MO Minimum : Elevators | (I) - Pits | (I)1 | Clean the pit. | 11/19/2024 |