Inspection
Inspection Details
Equipment ID
11681
11681
Inspection Date
9/21/2022
9/21/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Dixon Liljegren
Dixon Liljegren
Mechanic Name
Jason Turner
Jason Turner
Relief Valve Pressure
420
420
Slide
Governor Rope Pull
Door Closing Force
24F 30R
24F 30R
External ID
d47d770d-4249-481d-a6fc-94ef685bb651
d47d770d-4249-481d-a6fc-94ef685bb651
Location
Hodge Presbyterian Church
315 W Crowder Dr, Trenton, MO
Phone: (660) 359-5394
315 W Crowder Dr, Trenton, MO
Phone: (660) 359-5394
Owner
Attn: Hodge Presbyterian Church
Hodge Presbyterian Church
315 W Crowder, Trenton, MO 64683
Phone: (000) 000-0000
Hodge Presbyterian Church
315 W Crowder, Trenton, MO 64683
Phone: (000) 000-0000
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | Provide maintenance control plan that documents maintenance tasks and testing of elevator equipment. | 12/19/2024 | ||
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | Post firefighter operating instructions on car operating panel | 12/19/2024 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | Install cylinder oil collection containers of no more than 5 gallon capacity in pit. | 12/19/2024 | ||
| A17.1-2016 : Elevators | 2.34 - Flexible Hydraulic Hose and Fitting Assemblies | 8.6.5.6 | Replace flexible hydraulic hose located between control valve and cylinder. Existing hose has been in use for more than 6 years. | 12/19/2024 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | In case of fire don't use elevator signage needed | 12/19/2024 | ||
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | Machine room door needs to be self-locking | 12/19/2024 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | x | FDP is over 30 lbs | 9/21/2022 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | MCP needed | 12/19/2024 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | Provide MCP in machine room to log maintenance, repairs, and inspections. | 12/19/2024 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | Provide an up to date fire extinguisher in machine room. | 12/19/2024 | ||
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post current operating certificate in machine room. | 12/19/2024 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.1 Examination and Maintenance | x | Oil leakage from Victaulic fitting in pit shall be corrected with leaking gasket being replaced. | 9/9/2024 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | x | Alarm bell not working with 110 power off. Elite works. | 9/9/2024 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | MCP has not been initiated. | 12/19/2024 | ||
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Current State Operating Certificate not available. | 12/19/2024 | ||
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Current State Operating Certificate not available. Violations from 9/ 2023 annual inspection have been corrected. | 12/19/2024 |