Inspection
Inspection Details
Equipment ID
1463
1463
Inspection Date
9/21/2022
9/21/2022
Inspection Type
Reinspection
Reinspection
Inspector Name
Steven Salabay
Steven Salabay
Mechanic Name
Matthew Moon
Matthew Moon
Relief Valve Pressure
Slide
29
29
Governor Rope Pull
50/210
50/210
Door Closing Force
24/4
24/4
External ID
35ddc447-6844-445f-833c-22702b5333a2
35ddc447-6844-445f-833c-22702b5333a2
Location
Centene Place A
7711 Carondelet Ave, Clayton, MO
Phone: (314) 565-2824
Alt Phone: (314) 721-8427
Fax: (314) 721-8533
7711 Carondelet Ave, Clayton, MO
Phone: (314) 565-2824
Alt Phone: (314) 721-8427
Fax: (314) 721-8533
Owner
Attn: Property Manager
Centene Plaza c/o Rafco Properties
7700 Forsyth Blvd, Ste 100, Clayton, MO 63105
Phone: (314) 721-8427
Email: ONSITE@RAFCOPROP.COM
Centene Plaza c/o Rafco Properties
7700 Forsyth Blvd, Ste 100, Clayton, MO 63105
Phone: (314) 721-8427
Email: ONSITE@RAFCOPROP.COM
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post current State operating certificate in machine room | 7/8/2020 | ||
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | All the on site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. | 10/6/2025 | ||
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 1001.2(a)(17) | x | The emergency/standby power operation of the elevator shall be tested. | 2/18/2022 | |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1002.2f | x | Fire service operation shall be tested. | 2/18/2022 | |
| A17.1-1996 : Elevators | 2.11 - Disconnecting Means and Control | 210.4 | The 120VAC car lighting branch circuit shall not supply the recently installed in-car information displays. | 10/6/2025 | ||
| A17.1-1996 : Elevators | 2.9 - Guarding of exposed auxiliary equipment | 104.1 | Kick angles shall be installed around the machine room cable slots to keep items from falling into the hoistway. | 10/6/2025 | ||
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | A category 5 test shall be performed. | 2/18/2022 | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | This elevator is overdue for a full load test. A category 5 test shall be performed and witnessed. | 3/5/2022 | |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 1001.2(a)(17) | x | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 3/5/2022 | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Fire service shall be tested to complete the annual inspection. | 3/5/2022 | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | This elevator is overdue for a full load test. A category 5 test shall be performed and witnessed. | 9/21/2022 | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Fire service shall be tested to complete the annual inspection. | 9/21/2022 | |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post a current MO State operating certificate in the elevator machine room. | 10/6/2025 |