Inspection
Inspection Details
Equipment ID
8650
8650
Inspection Date
11/29/2021
11/29/2021
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Thomas McGrath
Thomas McGrath
Mechanic Name
James DeBell
James DeBell
Relief Valve Pressure
Slide
7 1/2
7 1/2
Governor Rope Pull
70/850
70/850
Door Closing Force
25
25
External ID
30b48507-2e84-4072-a20a-d0ed47f80b30
30b48507-2e84-4072-a20a-d0ed47f80b30
Location
Clayton Corporate Park Management Company
600 Corporate Park Dr, Clayton, MO
Phone: (000) 000-0000
600 Corporate Park Dr, Clayton, MO
Phone: (000) 000-0000
Owner
Attn: Clayton Corp Park Management Company
Clayton Corp Park Management Company
700 Corporate Park Dr, Clayton, MO 63105
Phone: (000) 000-0000
Clayton Corp Park Management Company
700 Corporate Park Dr, Clayton, MO 63105
Phone: (000) 000-0000
Billing
Attn: Clayton Corp Park Management Company
Clayton Corp Park Management Company
600 Corporate Park Dr, Clayton, MO 63105
Phone: (000) 000-0000
Clayton Corp Park Management Company
600 Corporate Park Dr, Clayton, MO 63105
Phone: (000) 000-0000
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | x | Replace hoist cables due to diameter reduction. | 9/16/2019 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | Written maintenance control program shall be kept on site for each elevator. | 12/18/2020 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.5 Code Data Plate | There is no code data plate found on the equipment to indicate the code and edition that the elevator was installed to (A17.1 1993), as used for all inspections. Provide a proper plate on the front of the controller or mainline disconnect. | 10/1/2025 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | x | The elevator ADA telephone inside the elevator is not working properly. Two-way communication could not be established. Repair/replace this phone for proper operation and passenger safety. Reinspection required. | 9/10/2024 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | The smoke detector at the top of the hoistway has become detached and shall be resecured in the electrical junction box. | 10/1/2025 | ||
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | x | This elevator has a backup emergency generator power that is used in case of a power outage. This system shall be scheduled to be tested and a reinspection is required. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Reinspection required. | 9/10/2024 | |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | x | Governor rope is rouged and undersized. Need to replace the governor rope. Re-inspection required | 10/1/2025 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.5 Code Data Plate | There is no code data plate found on the equipment to indicate the code and edition that the elevator was installed to (A17.1 1993), as used for all inspections. Provide a proper plate on the front of the controller or mainline disconnect. | 10/1/2025 | ||
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | x | The elevator ADA phone is not working. Re-inspection required | 10/1/2025 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | The smoke detector at the top pf the hoistway has become detached and shall be secured to the electrical junction box. | 10/1/2025 | ||
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | x | This elevator has a backup emergency generator power that is used in case of a power outage. This system shall be scheduled to be tested and a reinspection is required. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Re-inspection required | 10/1/2025 | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | x | The elevator ADA phone is not working. Re-inspection required | ||
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | The smoke detector at the top of the hoistway has become detached and shall be resecured in the electrical junction box. | |||
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | x | Governor rope is rouged and undersized. Need to replace the governor rope. Re-inspection required |