Inspection
Inspection Details
Equipment ID
23578
23578
Inspection Date
9/22/2022
9/22/2022
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Thomas Sharp
Thomas Sharp
Mechanic Name
Jeff Setchfield
Jeff Setchfield
Relief Valve Pressure
Slide
12.5
12.5
Governor Rope Pull
40 / 200
40 / 200
Door Closing Force
19
19
External ID
4ddc4728-d262-4e36-9fa7-0d800064e50a
4ddc4728-d262-4e36-9fa7-0d800064e50a
Location
Everly on the Loop
6105 Delmar Blvd, St. Louis, MO
Phone: (314) 896-4660
Email: byost@everlyontheloop.com
6105 Delmar Blvd, St. Louis, MO
Phone: (314) 896-4660
Email: byost@everlyontheloop.com
Owner
Attn: GMH Capital Partners
Everly on the Loop
6105 Delmar Blvd, St. Louis, MO 63112
Phone: (314) 896-4660
Email: byost@everlyontheloop.com
Everly on the Loop
6105 Delmar Blvd, St. Louis, MO 63112
Phone: (314) 896-4660
Email: byost@everlyontheloop.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The elevator ADA telephone inside the elevator is not operating correctly. Check and repair the programming of this phone for proper operation and passenger safety. Reinspection required. | 1/5/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.13 - Governor,overspeed switch and seal | 8.11.2.1.2(bb) | Yes | No | The remote governor activation device does not operate. Without this device in operation a category 5 test cannot be performed which will be required in 2022. Repair or replace the governor activation switch to operate as required. Reinspection required. | 1/5/2022 |
| A17.1-2016 : Elevators | 2.12 - Controller Wiring, Fuses, Grounding, Etc. | 8.11.2.1.2(q) | No | No | The emergency rescue battery in the controller has not been changed since the installation date. The Manufacture’s written procedure is for replacement every 3 years. If the battery becomes depleted the elevator will automatically stop operating. Replace the battery of this elevator before it shuts down due to battery being depleted. | 10/28/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.13 - Governor,overspeed switch and seal | 8.11.2.1.2(bb) | Yes | No | Governor overspeed switch & seal, remoter governor activation device does not work. Re-inspection required | 9/22/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | 2 way communication is not working. Re-inspection required | 3/27/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | 10/28/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Provide MCP. | 10/28/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.12 - Controller Wiring, Fuses, Grounding, Etc. | 8.6.1.6.3 | No | No | Rescue batteries do not appear to have been replaced, provide. Also mark date on batteries and entry in MCP. | 10/28/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.9 Cleaning of Car Tops | No | No | Clean the car top. | 10/28/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.7 Cleaning of Hoistways and Pits | No | No | Clean down the hoistway. | 10/28/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Clean the pit. | 10/28/2025 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Provide testing of the elevator on emergency power. | 12/19/2024 |
| A17.1-2016 : Elevators | 4.12 - Standby power selection switch | 8.6.4.19.7 (Re-Inspection) | Yes | No | Provide testing of the elevator emergency power selector switch. | 12/19/2024 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 2.27.2.3 (Elevator Emergency Power Illuminated Signal) | No | No | Need to repair emergency power indicator jewel for proper operation. | 10/28/2025 |
| MO Minimum : Elevators | (J) - Counterweights | (J)1 | No | No | Need to shorten belts to achieve proper counterweight clearance in pit | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | Need to repair emergency power indicator jewel for proper operation. |