Inspection
Inspection Details
Equipment ID
12755
12755
Inspection Date
9/19/2022
9/19/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Sean Carmody
Sean Carmody
Mechanic Name
David Howerton
David Howerton
Relief Valve Pressure
275
275
Slide
Governor Rope Pull
Door Closing Force
16
16
External ID
807559a8-7091-4653-ad7a-61c429232fff
807559a8-7091-4653-ad7a-61c429232fff
Location
15801 Apartment Bldg
5801 Sunshine Dr, St. Louis, MO
Phone: (314) 991-1584
5801 Sunshine Dr, St. Louis, MO
Phone: (314) 991-1584
Owner
Attn: 15801 Apartment Bldg
15801 Apartment Bldg
5801 Sunshine Dr, St. Louis, MO 63109
Phone: (314) 991-1584
15801 Apartment Bldg
5801 Sunshine Dr, St. Louis, MO 63109
Phone: (314) 991-1584
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)4 | No | No | The distance from the car gate and the hoistway door cannot be over 5” per the A17.1 1955 edition as referenced by the Missouri Minimum Code for Existing Elevators (currently it is 6 1/4”). The distance from the hoistway door and the edge of the inner sill ledge cannot be over 3” per the A17.1 1955 edition as referenced by the Missouri Minimum Code for Existing Elevators (currently it is 3 1/2”). A guard shall be installed on each hoistway door to minimize these gaps that is at least a minimum of 30 inches high and be beveled back to the door at a minimum of a 45 degree angle. This item shall be corrected and reinspected within 10 days or the elevator will be locked out of service. | 10/9/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | There is no fire extinguisher in the machine room, as required. Provide an ABC type extinguisher of proper size for the room. | 10/9/2019 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | The elevator pit light and guard strikes the elevator when the elevator travels down to the car buffer. The pit light guard shall be reduced in length to provide proper clearance and the light fixture shall be repaired. | 10/9/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | There is no fire extinguisher in the machine room, as required. Provide an ABC type extinguisher of proper size for the room. | 10/9/2019 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | The elevator pit light and guard strikes the elevator when the elevator travels down to the car buffer. The pit light guard shall be reduced in length to provide proper clearance and the light fixture shall be repaired. | 10/9/2019 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)9 Capacity Plate | No | No | Post capacity in the elevator cab. | 1/15/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Fire extinguisher is outdated (1981) - service or replace. | 1/15/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. | 11/1/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The pit shall be kept clean and dry. Oil has accumulated on the pit floor. | 11/1/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. Note: The extinguisher is expired. | 10/5/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 10/5/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | The machine room lighting shall be operational. | 10/5/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | A capacity plate with the capacity listed in pounds shall be provided and prominently displayed in the car enclosure. | 10/5/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 8/27/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Machine room shall have proper fire extinguisher and shall have current monthly/annual test tag. |