Inspection
Inspection Details
Equipment ID
10060
10060
Inspection Date
9/27/2022
9/27/2022
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Bradley Rasnake
Bradley Rasnake
Mechanic Name
Jeff Setchfield
Jeff Setchfield
Relief Valve Pressure
Slide
17
17
Governor Rope Pull
100 / 450
100 / 450
Door Closing Force
40
40
External ID
fec900a2-97ba-4585-9cfe-a9515ebad0f9
fec900a2-97ba-4585-9cfe-a9515ebad0f9
Location
AT & T- Washington
3810 Washington Blvd, St. Louis, MO
Phone: (314) 781-1980
3810 Washington Blvd, St. Louis, MO
Phone: (314) 781-1980
Owner
Attn: Ken Gerry
AT&T
3810 Washington Blvd, St. Louis, MO 63108
Phone: (314) 602-5453
Email: kg233j@att.com
AT&T
3810 Washington Blvd, St. Louis, MO 63108
Phone: (314) 602-5453
Email: kg233j@att.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Replace or reinforce catwalk in pit | 2/20/2019 |
| conversion | conversion | n/a | No | No | No fire extinguisher in machine room | 2/20/2019 |
| conversion | conversion | conversion - reinspect | Yes | No | Adjust car door close pressure to under 30lb. | 11/16/2018 |
| conversion | conversion | n/a | No | No | Handi-box cover on cart top is missing | 2/20/2019 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)7 | No | No | The elevator car door closing force is over the maximum allowable force of 30lbs. Readjust door closing force to be less than 30lbs. Reinspection required. | 3/26/2024 |
| A17.1-2016 : Elevators | 3.28 - Counterweight and counterweight buffer | 8.11.2.1.3(m) | No | No | The bottom guide rollers on the counterweight are cracked and shall be replaced. | 3/26/2024 |
| A17.1-2016 : Elevators | 3.12 - Pipes, wiring, and ducts | 8.11.2.1.3(r) | No | No | A receptacle box is missing its cover plate on top of the car exposing electrical connections. The cover plate shall be reinstalled to limit accidental contact by maintenance and emergency personnel. | 3/26/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Counterweight guide rollers are deteriorated and causes unsafe condition. Re-inspection required | 3/26/2024 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)7 | Yes | No | Car door closing force is way above 30 lbs and shall be adjusted to 30 lbs or below. Re-inspection required | 3/26/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | Yes | No | Counterweight rollers are deteriorating and shall be replaced. Re-inspection required | 3/26/2024 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)7 | Yes | No | Car door force exceeds code, adjust as needed. | 3/26/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Top and bottom counterweight roller guides worn, replace as needed. | 12/11/2025 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | Car top electric junction box missing cover. | 12/11/2025 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Provide testing of the elevator on emergency power. | 3/26/2024 |
| A17.1-2016 : Elevators | 4.12 - Standby power selection switch | 8.6.4.19.7 (Re-Inspection) | Yes | No | Provide testing of the elevator emergency power selector switch (lobby). | 3/26/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Clean the car top. | 12/11/2025 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | Yes | Phase I recall not working, car removed from service. | 3/26/2024 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)7 | Yes | No | Door force exceeds code. | 1/7/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | Yes | No | Bottom c/w roller guides bad, replace. | 1/7/2025 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | Yes | No | Car top electric j/b missing cover. | 1/7/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone shall be made operational. Re-inspection required |