Inspection
Inspection Details
Equipment ID
8856
8856
Inspection Date
9/7/2018
9/7/2018
Inspection Type
Reinspection
Reinspection
Inspector Name
Jerry Eckhart
Jerry Eckhart
Mechanic Name
Relief Valve Pressure
NA
NA
Slide
Governor Rope Pull
Door Closing Force
NA
NA
External ID
64f7c367-69da-4f4a-b73a-ec36527b7277
64f7c367-69da-4f4a-b73a-ec36527b7277
Location
Huvepharma, Inc.
3360 MAURY AVE, SAINT LOUIS, MO
3360 MAURY AVE, SAINT LOUIS, MO
Owner
Huvepharma, Inc.
3360 MAURY AVE, SAINT LOUIS, MO 63116-2029
3360 MAURY AVE, SAINT LOUIS, MO 63116-2029
Billing
Attn: Huvepharma, Inc.
3360 MAURY AVE, SAINT LOUIS, MO 63116-2029
3360 MAURY AVE, SAINT LOUIS, MO 63116-2029
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7 | No | No | Provide 2.5 foot candles of lighting in elevator cab. C-5 | 11/1/2018 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Phone in elevator cab does not work. | 9/7/2018 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.2-211.8 | Yes | Yes | Phase I recall - When car returns to recall floor, the doors can still be opened and closed. Doors should open and remain open | 5/30/2019 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.2-211.8 | Yes | Yes | Fire service Phase II - Doors open and close automatically. Should be constant pressure open and close | 5/30/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency Phone in car fails to establish two-way communication | 4/28/2025 |
| A17.1-2016 : Elevators | 3.17 - Door and gate equipment | 8.6.4.13 | Yes | No | For vertical power closing doors with momentary or automatic closing. A warning bell or other audible signal shall be provided on the car which shall start to sound at least 5 seconds prior to the time the car door or gate starts to close and shall continue to sound until the hoistway door is substantially closed. | 4/28/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) | Yes | No | Overspeed valves, where provided, shall be inspected and tested to verify that they will stop the car, traveling down with rated load every 5 years. | 5/14/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency Phone in car fails to establish two-way communication | 5/14/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Provide a fire extinguisher in the elevator machine room | 5/14/2026 |
| A17.1-2016 : Elevators | 5.11 - Plunger and Cylinder | 8.6.5.5 | Yes | No | Where pressure piping, valves, and cylinders use packing glands or seals, they shall be examined and maintained to prevent excessive loss of fluid. The packing is losing oil in the pit. Replace packing | 5/14/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | A written Maintenance Control Program shall be in place to maintain the equipment in compliance with the requirements of Section 8.6. | 5/14/2026 |