Inspection
Inspection Details
Equipment ID
13344
13344
Inspection Date
9/5/2018
9/5/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Angelo Consiglio
Angelo Consiglio
Mechanic Name
Thomas Moore
Thomas Moore
Relief Valve Pressure
Slide
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
5b0dc52c-8486-4423-8d43-1d66f67ab2c6
5b0dc52c-8486-4423-8d43-1d66f67ab2c6
Location
Bevo Bottling Plant- Bldg #137
619 ARSENAL ST, SAINT LOUIS, MO
619 ARSENAL ST, SAINT LOUIS, MO
Owner
Attn: Derik Schwaegel
Anheuser Busch
1 BUSCH PL 137-2, SAINT LOUIS, MO 63118
Phone: (314) 713-7504
Anheuser Busch
1 BUSCH PL 137-2, SAINT LOUIS, MO 63118
Phone: (314) 713-7504
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (I) - Pits | (I)8 | No | No | Repair sump pump | 9/26/2025 |
| MO Minimum : Elevators | 2.3 - Lighting and receptacles | 110.27 Guarding of Live Parts NFPA 72 | No | No | Replace missing guards on machine room lights or provide tubes. | 9/26/2025 |
| MO Minimum : Elevators | (F) - Electrical Switches | (F)5 | Yes | No | Repair or replace damaged control switches. | 9/29/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Repair emergency phone | 9/29/2021 |
| A17.1-1996 : Elevators | 2.3 - Lighting and receptacles | 1001.2(b)(3) Inspection code | No | No | Replace missing guards on machine room lights or provide tubes | 9/26/2025 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7 | No | No | Replace cab light that has open wiring. Replace missing covers on cab lights | 9/26/2025 |
| A17.1-1996 : Elevators | 3.23 - Suspension rope | 1001.2(c)(29) | Yes | No | Suspension ropes are undersized. Reinspect in 120 days | 1/12/2023 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | Clean all debris out of pit | 9/26/2025 |
| A17.1-1996 : Elevators | 3.17 - Door and gate equipment | 1001.2(c)(23) | No | No | Bolt shut 8th floor rear door so that it will not open. Door is not in use | 9/26/2025 |
| A17.1-1996 : Elevators | 3.17 - Door and gate equipment | 1001.2(c)(23) | No | No | Safety light ray does not work. Door will not reopen with something in the way. Reinspect Required | 9/26/2025 |
| A17.1-1996 : Elevators | 3.17 - Door and gate equipment | 1001.2(c)(23) | No | No | In car rear door is off track and needs to be reattached and locked shut | 9/26/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.11 Runby (Re-Inspection) | Yes | No | Shorten hoist cables. Counterweight stricking buffers before final limit 14 day reinspection 11/14/23 | 10/17/2024 |