Inspection
Inspection Details
Equipment ID
9380
9380
Inspection Date
10/10/2022
10/10/2022
Inspection Type
Alteration
Alteration
Inspector Name
Wayne Coder
Wayne Coder
Mechanic Name
David Scott
David Scott
Relief Valve Pressure
415
415
Slide
Governor Rope Pull
Door Closing Force
n/a
n/a
External ID
56c7784b-1c6b-4ebf-b5c5-94e33901758f
56c7784b-1c6b-4ebf-b5c5-94e33901758f
Location
West County Center
80 W COUNTY CTR, SAINT LOUIS, MO
Phone: (314) 288-2020
80 W COUNTY CTR, SAINT LOUIS, MO
Phone: (314) 288-2020
Owner
Attn: Andrew Goldacker
CBL Properties/West County center
80 W County Center, Des Peres, MO 63131
Phone: (314) 288-2026
Alt Phone: (314) 409-8204
Email: andrew.goldacker@cblproperties.com
CBL Properties/West County center
80 W County Center, Des Peres, MO 63131
Phone: (314) 288-2026
Alt Phone: (314) 409-8204
Email: andrew.goldacker@cblproperties.com
Billing
Same as Owner
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
conversion | conversion | n/a | Post Mo Stae certificate in machine room | 10/22/2019 | ||
A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post current operating certificate in machine room. | 10/22/2019 | ||
A17.1-1996 : Elevators | 2.1 - Access to machine space | 1001.2(b)(1) | Machine room needs to be locked at all times. | 10/22/2019 | ||
A17.1-1996 : Elevators | 3.17 - Door and gate equipment | 1001.2(c)(23) | Top level door is missing two door gibs. | 10/22/2019 | ||
A17.1-1996 : Elevators | 3.17 - Door and gate equipment | 210.1e | Gate switch exceeds minimum measurement for center opening doors. Reinspect. | 10/22/2019 | ||
A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 1206.2a (Pits and Hoistways) | There needs to be a working lit in the pit. | 10/22/2019 | ||
A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency light not working. | 11/20/2019 | |
A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency alarm bell not working. | 11/20/2019 | |
A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post current operating certificate in machine room. | 10/22/2019 | ||
A17.1-1996 : Elevators | 1.7 - Car door or gate | 1001.2(a)(7) | x | Adjust car door to cab clearance to 3/8 max - currently in excess of 1/2 inch. | 9/28/2020 | |
A17.1-1996 : Elevators | 3.17 - Door and gate equipment | 1001.2(c)(23) | Replace missing door gibbs on 5th floor and missing fire tab on 3rd floor. | 9/28/2020 | ||
A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1206.1h | Annual tag shows expired. | 11/30/2022 | ||
A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Alarm bell does not work on 110v emergency power or normal power | 4/9/2024 | |
A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | x | Emergency light in the cab does not work | 4/9/2024 | |
A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | Provide existing pit light to work. | |||
A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1206.1h | Provide current year tested fire extinguisher in the elevator machine room. | |||
A17.1-1996 : Elevators | 3.2 - Car top light and outlet | 204.7 | Provide car top light to work. | |||
A17.1-1996 : Elevators | 3.8 - Top emergency exit | 204.1e | Provide means to secure car top exit. | |||
A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1002.2f | x | Provide,on Phase II operations, call cancel feature to work. |