Inspection
Inspection Details
Equipment ID
16951
16951
Inspection Date
10/13/2022
10/13/2022
Inspection Type
Reinspection
Reinspection
Inspector Name
Ronald Edwards
Ronald Edwards
Mechanic Name
Bruce Dorsey
Bruce Dorsey
Relief Valve Pressure
n/a
n/a
Slide
Governor Rope Pull
Door Closing Force
n/a
n/a
External ID
e8c09f80-d4ad-46e0-b48a-4f70cc116d2b
e8c09f80-d4ad-46e0-b48a-4f70cc116d2b
Location
Independence Center
2035 E Independence Center Dr, Independence, MO
Phone: (816) 795-8602
2035 E Independence Center Dr, Independence, MO
Phone: (816) 795-8602
Owner
Attn: IGP Business Group
IGP Business Group
5919 W 3rd St, Ste B, Los Angeles, CA 90036
Phone: (816) 795-8602
IGP Business Group
5919 W 3rd St, Ste B, Los Angeles, CA 90036
Phone: (816) 795-8602
Billing
Attn: Independence Mall Holding LLC
Independence Mall Holding LLC
18801 E 39th St S, Ste 2035, Independence, MO 64057
Phone: (816) 795-8602
Email: thueser@shopindependencecenter.com
Independence Mall Holding LLC
18801 E 39th St S, Ste 2035, Independence, MO 64057
Phone: (816) 795-8602
Email: thueser@shopindependencecenter.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | emg phone not working | 4/14/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | no cirt. of operation displayed | |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | phone not working | 10/13/2022 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.2 Phase I Operation Recall by Initiating Device | Yes | Yes | fire int.devices in mach room not working bypassed | 10/13/2022 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.2 On-Site Documentation | No | No | mcp not being maintained | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | no current cirt. posted | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | No | No | wiring not pertaing to elev hanging dn below celing | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room door not self closing or self locking | |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.2-211.8 | Yes | Yes | machroom is at designated level smoke det. in mach room dosnt send car to alternate level as it should. 2.11.3b(2) | 11/30/2022 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | phone not working | 3/20/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | no current. cirt. displayed | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | debris on machroom floor | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | materials not necessary for the maint of the elev. shall not be stored in machroom | |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | phone was answered but security couldnt tell me my location | 2/4/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | pit has about 18 inches of standind water in it. Red Tagged | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | door key for machine room dosnt work the lock | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | needs to be cleaned an sump cover put back on | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Mach room floor dirty |