Inspection
Inspection Details
Equipment ID
15218
15218
Inspection Date
10/13/2022
10/13/2022
Inspection Type
Alteration
Alteration
Inspector Name
Michael Bailey
Michael Bailey
Mechanic Name
Ross Colligan
Ross Colligan
Relief Valve Pressure
Slide
na
na
Governor Rope Pull
50 / 900
50 / 900
Door Closing Force
na
na
External ID
21cef1c0-b9a0-485c-b476-6c77eba0433a
21cef1c0-b9a0-485c-b476-6c77eba0433a
Location
Frisco Building
906 Olive St, St. Louis, MO
Phone: (314) 432-2222
906 Olive St, St. Louis, MO
Phone: (314) 432-2222
Owner
Attn: Maria Pressley
Cas-Mizzou-Neda, LLC
906 Olive Street, PH #3, St. Louis, MO 63101
Phone: (314) 621-7300
Email: mariafrisco906@gmail.com
Cas-Mizzou-Neda, LLC
906 Olive Street, PH #3, St. Louis, MO 63101
Phone: (314) 621-7300
Email: mariafrisco906@gmail.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (F) - Electrical Switches | (F)1 | Yes | No | Cab stop switch alarm inoperative. Repair | 1/23/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Replace sheave liners. | 1/16/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Hands free cab phone inoperative. Repair - possible lost signal. | 12/9/2020 |
| MO Minimum : Elevators | (A) - Hoistways | (A)13 | No | No | Replace drywall in hoistway that has been cut out on 3rd floor. | 1/16/2025 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | Yes | Phase II does not work in car. Repair within ten (10) days or red tag unit. | 7/1/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Cat 5 full load testing is overdue. Perform required testing. Re-inspection required | 12/22/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 1/16/2025 |
| A17.1-2016 : Elevators | 2.13 - Governor, Overspeed Switch, and Seal | 2.18.9 | Yes | No | Overspeed governor was replaced at an earlier time and was recalibrated, but the data plate was not changed to reflect changed. Replace plate with one that has correct information. Re-inspection required, but can be performed at a time of completion of 5 yr testing | 2/13/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | 5 year inspection was started, but not completed. Need to preform full load full speed car safeties, 125% brake test, full load full speed car buffer, counterweight buffer, governor rope pull out, governor rope pull thru. Re-inspection required within 90 days | 2/13/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Cat 5 testing incomplete - governor trip speeds need tested and car set on safeties to complete cat 5 testing | 2/28/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 1/16/2025 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Both alarm bell buttons are not working correctly, need to be replaced. Re-inspection required | 12/4/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 1/16/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 1/16/2025 |