Inspection
Inspection Details
Equipment ID
20205
20205
Inspection Date
10/17/2022
10/17/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Thomas Krug
Thomas Krug
Mechanic Name
James DeBell
James DeBell
Relief Valve Pressure
Slide
n/a
n/a
Governor Rope Pull
n/a
n/a
Door Closing Force
25
25
External ID
ca3bc1ae-72df-41da-b326-8962f13b2ffe
ca3bc1ae-72df-41da-b326-8962f13b2ffe
Location
Warehouse 7 Lofts
1227 Washington Ave, St. Louis, MO
Phone: (314) 621-8440
Alt Phone: (314) 323-7326
1227 Washington Ave, St. Louis, MO
Phone: (314) 621-8440
Alt Phone: (314) 323-7326
Owner
Attn: 1227 Washington LLC
1227 Washington LLC
1314 Washington Ave, St. Louis, MO 63103
Phone: (000) 000-0000
Email: matt@mbdstl.com
1227 Washington LLC
1314 Washington Ave, St. Louis, MO 63103
Phone: (000) 000-0000
Email: matt@mbdstl.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.23 - Suspension rope | 8.11.2.1.3(cc) | No | No | Hoist ropes are rouged and nearing minimum diameter and shall be replaced within 90 days. | 10/9/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 8.11.2.1.2(a) | No | No | Machine room door closer shall work. | 10/9/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall work with 24/7 support. | 10/9/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state operating certificate. | 10/9/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.23 - Suspension rope | 8.11.2.1.3(cc) | No | No | The suspension ropes have significant rouge and are nearing the minimum diameter. Replace the hoist ropes. | 10/9/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 2.7.3.4 | No | No | The machine room door shall be self-closing. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.23 - Suspension rope | 8.11.2.1.3(cc)(3) Replace when diameter is reduced (Re-Inspection) | Yes | No | The hoist ropes are rouged and approaching the minimum diameter. The hoist ropes shall be replaced. | 3/29/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2 Design and Construction of Pits | No | No | The pit shall be kept dry. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | The car top shall be kept clean. Clean the car top. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | An ABC fire extinguisher with a current test tag shall be provided in the elevator machine room. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency Phone in car fails to establish two-way communication | 10/17/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | All pits shall be kept dry, clean, and free of equipment or material not relating to the operation of the elevator. (Water accumulating in pit) | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency Phone in car fails to establish two-way communication (dials but does not connect) | 8/3/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | There is no state operating certificate in the machine room. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | The fire extinguisher is expired. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | The pit shall be kept clean and dry. Remove water from pit floor. | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | The machine room door shall be self closing. | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | The machine room door shall be self closing. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | The Emergency Phone in the car fails to establish two-way communication. The phone dials an inactive number. |