Inspection
Inspection Details
Equipment ID
8651
8651
Inspection Date
9/23/2022
9/23/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Kurt Zimmerman
Kurt Zimmerman
Mechanic Name
James DeBell
James DeBell
Relief Valve Pressure
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
22
22
External ID
c42062fa-674e-4d2b-825d-371dee4b4168
c42062fa-674e-4d2b-825d-371dee4b4168
Location
Clayton Corporate Park Management Company
600 Corporate Park Dr, Clayton, MO
Phone: (000) 000-0000
600 Corporate Park Dr, Clayton, MO
Phone: (000) 000-0000
Owner
Attn: Clayton Corp Park Management Company
Clayton Corp Park Management Company
700 Corporate Park Dr, Clayton, MO 63105
Phone: (000) 000-0000
Clayton Corp Park Management Company
700 Corporate Park Dr, Clayton, MO 63105
Phone: (000) 000-0000
Billing
Attn: Clayton Corp Park Management Company
Clayton Corp Park Management Company
600 Corporate Park Dr, Clayton, MO 63105
Phone: (000) 000-0000
Clayton Corp Park Management Company
600 Corporate Park Dr, Clayton, MO 63105
Phone: (000) 000-0000
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | Written maintenance control program shall be kept on site for each elevator. | 12/18/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Repair phone in car | 9/23/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.5 Code Data Plate | No | No | There is no code data plate found on the equipment to indicate the code and edition that the elevator was installed to (A17.1 1993), as used for all inspections. Provide a proper plate on the front of the controller or mainline disconnect. | 10/1/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | The elevator ADA telephone inside the elevator is not working properly. Two-way communication could not be established. Repair/replace this phone for proper operation and passenger safety. Reinspection required. | 9/10/2024 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | A17.1 2016-8.6.4.19.6 The fireman's emergency service phase I and II operations was tested and the following deficiency was noted: - The proximity door protection device is not rendered inoperative when phase I operation is initiated. | 9/10/2024 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | This elevator has a backup emergency generator power that is used in case of a power outage. This system shall be scheduled to be tested and a reinspection is required. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Reinspection required. | 9/10/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | The smoke detector at the top of the hoistway has become detached and shell be secured to the electrical junction box. | 10/1/2025 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Governor rope is rouged and undersized. Need to replace governor rope. Re-inspection required | 10/1/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.5 Code Data Plate | No | No | There is no code data plate found on the equipment to indicate the code and edition that the elevator was installed to (A17.1 1993), as used for all inspections. Provide a proper plate on the front of the controller or mainline disconnect. | 10/1/2025 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | The elevator has a backup emergency generator power that is used in case of a power outage. This system shall be scheduled to be tested and reinspection is required. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Re-inspection required | 10/1/2025 |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | No | No | The smoke detector at the top of the hoistway has become detached and shall be re-secured to the electrical junction box. | 10/9/2025 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | Yes | The governor rope is rouged and undersized. Red-tagged, Re-inspection required | |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | No | No | The smoke detector at the top of the hoistway has become detached and shall be re-secured to the electrical junction box. |