Inspection
Inspection Details
Equipment ID
10053
10053
Inspection Date
9/6/2018
9/6/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Clyde Johnson
Clyde Johnson
Mechanic Name
Robert Kehm
Robert Kehm
Relief Valve Pressure
Slide
Governor Rope Pull
NA
NA
Door Closing Force
22
22
External ID
a8dccdf8-5603-4e19-8704-7ce35cfc3591
a8dccdf8-5603-4e19-8704-7ce35cfc3591
Location
Barry-Wiehmiller
8020 FORSYTH BLVD, CLAYTON, MO
8020 FORSYTH BLVD, CLAYTON, MO
Owner
Barry-Wiehmiller Companies, INC.
8020 FORSYTH BLVD, CLAYTON, MO 63105-1707
8020 FORSYTH BLVD, CLAYTON, MO 63105-1707
Billing
Attn: Barry-Wiehmiller Companies, INC.
8020 FORSYTH BLVD, CLAYTON, MO 63105-1707
8020 FORSYTH BLVD, CLAYTON, MO 63105-1707
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (M) - Car Safeties and Speed Governors | (M)1 | Yes | Yes | Test car safeties with rated load. | 12/17/2019 |
| MO Minimum : Elevators | (D) - Brakes | (D)1 | Yes | Yes | Test brake with 125% of rated load. Reinspect within 30 days. | 12/17/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Written maintenance control program shall be kept on site for each elevator. | 9/22/2021 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 6/29/2023 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Elevator cab phone does not work, needs repaired. Re-inspection required | 10/4/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the elevator machine room | 10/4/2024 |
| A17.1-2016 : Elevators | 2.43 - Emergency Brake, Ascending Car Overspeed, and Unintended Car Movement Protection | 8.6.4.20.11 (Re-Inspection) | Yes | Yes | Performed unintended movement test. Car movement in the down direction with 125% of rated load was 87 inches. Movement in the up direction with no load was 56 inches. Elevator must not move more than 48 inches. Red-tagged, removed from service. Re-inspection required | 10/4/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Need to test car safeties at rated speed with rated load. Re-inspection required | 10/4/2024 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | Yes | No | Water is entering pit and causing counterweight buffer, car buffer, and bottom of rails to rust. | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Phone not working. Line is dead in machine room. |