Inspection
Inspection Details
Equipment ID
13859
13859
Inspection Date
10/19/2022
10/19/2022
Inspection Type
Reinspection
Reinspection
Inspector Name
Thomas Sharp
Thomas Sharp
Mechanic Name
James DeBell
James DeBell
Relief Valve Pressure
Slide
20"
20"
Governor Rope Pull
na
na
Door Closing Force
na
na
External ID
f71846ca-bfd2-42c1-8365-a4f60c8e8efe
f71846ca-bfd2-42c1-8365-a4f60c8e8efe
Location
Hollywood Casino St. Louis
777 Casino Center Dr, Maryland Heights, MO
Phone: (314) 770-8278
777 Casino Center Dr, Maryland Heights, MO
Phone: (314) 770-8278
Owner
Attn: John Koshinski
Hollywood Casino St. Louis
777 Casino Center Dr, Maryland Heights, MO 63043
Phone: (314) 770-8278
Email: John.Koshinski@pngaming.com
Hollywood Casino St. Louis
777 Casino Center Dr, Maryland Heights, MO 63043
Phone: (314) 770-8278
Email: John.Koshinski@pngaming.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | Hold position does not work on phase 2 fire service | 8/7/2018 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit shall be kept clean. | 8/22/2019 |
| MO Minimum : Elevators | (F) - Electrical Switches | (F)3 | Yes | No | Machine room run switch (up and down) shall return to the neutral position. | 10/5/2020 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Diameter loss due to rouging exceeds proposed criteria | 10/5/2020 |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | Yes | No | Fireman's recall needs to be tested. | 10/5/2020 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean pit. | 10/10/2020 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Test counterweight buffer at rated speed. Re-inspection required | 10/19/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Test car buffer, rated load & speed. Re-inspection required | 10/19/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Test car safeties, rated load & speed. Re-inspection required | 10/19/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Test machine brake with 125% rated load. Re-inspection required | 10/19/2022 |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | No | No | Replace missing phase I and II fire service operating instructions signs. | 7/23/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | Elevator car door restrictor does not work, needs repaired. Re-inspection required | 7/23/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 7/23/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | No | No | Replace missing phase I and II fire service operating instructions signs. |