Inspection
Inspection Details
Equipment ID
25902
25902
Inspection Date
10/15/2022
10/15/2022
Inspection Type
Reinspection
Reinspection
Inspector Name
Michael Gallaher
Michael Gallaher
Mechanic Name
Benjamin Postawko
Benjamin Postawko
Relief Valve Pressure
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
na
na
External ID
3799c50b-d3b0-4607-bbba-b237bab3539c
3799c50b-d3b0-4607-bbba-b237bab3539c
Location
Doorways 2.0 Admin
1101 N Jefferson Ave, St. Louisi, MO
Phone: (314) 535-1919 Ext: 2701
Email: info@doorwayshousing.org
1101 N Jefferson Ave, St. Louisi, MO
Phone: (314) 535-1919 Ext: 2701
Email: info@doorwayshousing.org
Owner
Attn: Opal Jones
Doorways 2.0 Services
4385 Maryland Ave, St. Louis, MO 63108
Phone: (314) 535-1919 Ext: 2701
Email: info@doorwayshousing.org
Doorways 2.0 Services
4385 Maryland Ave, St. Louis, MO 63108
Phone: (314) 535-1919 Ext: 2701
Email: info@doorwayshousing.org
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.3 | Yes | No | Heat detector shall be installed not more than 24" from sprinkler head. Re-inspection required | 10/4/2022 |
| A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 2.7.9.1 | Yes | No | Lighting in front of the controller, panel shall be of at least 19 fc and the pit shall have at least 10 fc at farthest point of light. Re-inspection required | 10/4/2022 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2.3 | Yes | No | Sump pump needs to be wired for proper operation. Re-inspection required | 10/4/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | No recall device tested, no one there to perform test. Video monitoring needs to be tested, no internet. Re-inspection required | 10/4/2022 |
| A17.1-2016 : Elevators | 2.4 - Machine space | 8.6.4.8 Machine Room and Machinery Space | Yes | No | Access and working space shall be provided and maintained about all electrical equipment to permit ready & safe operation and maintenance of such equipment | 10/4/2022 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.5 | Yes | No | Pit illumination to be 10fc minimum | 10/15/2022 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 3.27.1 Phase I Emergency Recall Operation After Device Actuation | Yes | Yes | Test all recall devices | 10/15/2022 |
| A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.3 | No | No | 2.8.3.3.2 Device when activated shall remove the power to the disconnect prior to the application of water | 2/5/2024 |
| A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.2 | No | No | Electrical wiring shall meet NFPA 70 Disconnects shall have sorce location labeled on them | 2/5/2024 |
| A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.2 | No | No | Disconnects per NFPA shall have 36in front and 30in side clear and unobstructed. Close hole in floor in front of the discinnect | 2/5/2024 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 2.11.1.3 Emergency Phone not workng Alarm Functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone calls out cannot make audio or visual contact. | 12/18/2024 |