Inspection
Inspection Details
Equipment ID
6359
6359
Inspection Date
10/17/2022
10/17/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Gallaher
Michael Gallaher
Mechanic Name
Jeffrey Miller
Jeffrey Miller
Relief Valve Pressure
515
515
Slide
Governor Rope Pull
Door Closing Force
25
25
External ID
d82b1a28-53ae-4afa-9d30-54de122bfb7e
d82b1a28-53ae-4afa-9d30-54de122bfb7e
Location
Alpha Terrace Apartments
6105 ETZEL AVE, SAINT LOUIS, MO
Phone: (314) 862-5668
6105 ETZEL AVE, SAINT LOUIS, MO
Phone: (314) 862-5668
Owner
Attn: Alpha Terrace Development Corp
Alpha Terrace Development Corp
6105 Etzel Ave, St. Louis, MO 63133
Phone: (000) 000-0000
Email: lillie@alphaterraceapartments.com
Alpha Terrace Development Corp
6105 Etzel Ave, St. Louis, MO 63133
Phone: (000) 000-0000
Email: lillie@alphaterraceapartments.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-2016 : Elevators | 1.5 - Car lighting and receptacles | 2.14.7 | No | No | The cab ceiling is of the open egg-crate type, which does not provide protection from the light bulbs should they shatter. The lights shall be guarded by plastic sleeve or some other means to properly protect passengers. | 5/4/2022 |
| A17.1-2016 : Elevators | 2.5 - Housekeeping | 8.11.3.1.2(h) | No | No | The elevator machine room cannot be used for storage. Remove the items being stored in the machine room to provide proper room for maintenance to be performed. | 5/4/2022 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | The elevator pit shall be cleaned of oil and water. | 5/4/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator has an overspeed valve device installed that is not sealed and is now required to have a 5 year full load test performed. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Reinspection is required. | 5/4/2022 |
| A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 8.11.3.1.2(f) | No | No | A machine room light fixture above the hydraulic equipment is not functioning. Repair lighting fixture to provide adequate lighting for maintenance and emergency personnel. | 5/4/2022 |
| A17.1-2016 : Elevators | 1.5 - Car lighting and receptacles | 2.14.7 | No | No | Ceiling panels in car are open egg crate type, providing no protection for passengers in event of bulb breakage. Panels should be replaced with solid type, plastic tubes & endcaps should be installed over bulbs or other means provided to protect passengers | 12/14/2022 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Clean oil & water from pit | 12/14/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit light is not working, repair same | 12/14/2022 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Phone in elevator cab does not work. Re-inspection required | 2/17/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Phone is not working in elevator, no two way communication. Re-inspection required | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency light is not working with loss of 110. Re-inspection required |