Inspection
Inspection Details
Equipment ID
11084
11084
Inspection Date
9/11/2018
9/11/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Steven Salabay
Steven Salabay
Mechanic Name
Relief Valve Pressure
Slide
Governor Rope Pull
NA/NA
NA/NA
Door Closing Force
26
26
External ID
7cbc70d1-f7ec-4d27-be58-1b7ef8e87242
7cbc70d1-f7ec-4d27-be58-1b7ef8e87242
Location
Centene
7733 CARONDELET AVE, CLAYTON, MO
7733 CARONDELET AVE, CLAYTON, MO
Owner
Centene
7733 CARONDELET AVE, CLAYTON, MO 63105-3309
7733 CARONDELET AVE, CLAYTON, MO 63105-3309
Billing
Attn: Centene
7711 CARONDELET AVE STE 303, CLAYTON, MO 63105-3313
7711 CARONDELET AVE STE 303, CLAYTON, MO 63105-3313
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.11 - Disconnecting Means and Control | 2.26.4 | x | Provide feeder locations on main line connects. | 1/31/2020 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 8.11.2.1.2(c) | x | Provide code compliant machine room lighting. Currently measured at 14.5fc. | 1/31/2020 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 8.11.2.1.2(c) | x | Provide GFCI type receptacle on lower part of machine room. | 1/31/2020 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 8.11.2.1.2(h) | x | Secure wires hanging down from over the machine room door. | 1/31/2020 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.9 - Floor and emergency identification numbering | 8.11.2.1.3(o) | x | Provide numbering on the car top. | 1/31/2020 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.4 - Top-of-car Clearance, Refuge Space, & Standard Railing | 8.6.4.11 | x | 2.10.2 - Provide car top railing system, as needed. | 1/31/2020 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | x | Provide complete MCP. | 1/31/2020 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.11.2.1.2(e) (Re-Inspection) | x | Remove all non-elevator related materials from the machine room. | 1/31/2020 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.17 - Drive machine brake | 8.11.2.1.2(o) | x | Provide testing of machine brake with 125% capacity. | 1/31/2020 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.20 - Governor rope | 8.11.2.1.3(z) | x | Provide governor rope data tag. | 1/31/2020 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.23 - Suspension rope | 8.11.2.1.3(cc) | x | Provide hoist rope data tag. | 1/31/2020 | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Must have current certificate in machine room. | 10/6/2025 |