Inspection
Inspection Details
Equipment ID
19055
19055
Inspection Date
8/7/2018
8/7/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
David Howerton
David Howerton
Relief Valve Pressure
245
245
Slide
Governor Rope Pull
Door Closing Force
26
26
External ID
fff51f44-53c0-4071-adbb-23f970b19a39
fff51f44-53c0-4071-adbb-23f970b19a39
Location
Locust Street Lofts Apts
414 N 23RD ST, SAINT LOUIS, MO
414 N 23RD ST, SAINT LOUIS, MO
Owner
Locust Motor LLC
4300 CHURCH RD, CENTREVILLE, IL 62207-1378
4300 CHURCH RD, CENTREVILLE, IL 62207-1378
Billing
Attn: Locust Motor LLC
4300 CHURCH RD, CENTREVILLE, IL 62207-1378
4300 CHURCH RD, CENTREVILLE, IL 62207-1378
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.37 - Pressure Switch | 3.26.8 Pressure Switch | x | Where the top of the cylinder is installed above the top of the storage tank, a pressure switch shall be provided according to A17.1 - 3.26.8 | 11/20/2020 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | The in car emergency telephone shall be operational. | 11/20/2020 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 2.14.7.1.3 Provide Auxiliary Lighting | x | The emergency light shall be operational. | 11/20/2020 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | The alarm bell shall be operational under auxiliary power. | 11/20/2020 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 9/23/2021 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | Written evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site. | 9/23/2021 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.14 - Code data plate | 8.9 | Install a code data plate. It shall read: A17.1-1996 | 9/23/2021 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.11 - Disconnecting Means and Control | 8.11.2.1.2(k) | The disconnect located in the machine room shall be provided with a sign to identify the location of the supply side overcurrent protective device. | 9/23/2021 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | Clean the pit of oil, dirt, and debris. | 9/23/2021 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | The hall call box located on the 1st floor landing is pulling away from the wall. Take corrective action as needed. | 9/23/2021 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. | 11/22/2022 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 11/22/2022 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.9 Elevator Corridor Call Station Pictograph | Each floor shall have "In Case of Fire Use Stairs" signage. | 11/22/2022 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | The in car emergency telephone shall be operational and code compliant. | 11/15/2022 | |
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | "In Case of Fire" signage is required at each floor. (On order per building contact) | 12/7/2022 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency phone shall be operational. | 9/5/2024 |