Inspection
Inspection Details
Equipment ID
12488
12488
Inspection Date
9/17/2018
9/17/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Herbert Neulist
Herbert Neulist
Mechanic Name
Scott Fischer
Scott Fischer
Relief Valve Pressure
300
300
Slide
Governor Rope Pull
Door Closing Force
28
28
External ID
a85bae90-55da-47f7-a1de-67a814d01213
a85bae90-55da-47f7-a1de-67a814d01213
Location
Villa Dorado Condo
11872 CRESTA VERDE DR, SAINT LOUIS, MO
11872 CRESTA VERDE DR, SAINT LOUIS, MO
Owner
Grier Management Group
1400 ELBRIDGE PAYNE RD STE 210, CHESTERFIELD, MO 63017-8520
1400 ELBRIDGE PAYNE RD STE 210, CHESTERFIELD, MO 63017-8520
Billing
Attn: Grier Management Group
1400 ELBRIDGE PAYNE RD STE 210, CHESTERFIELD, MO 63017-8520
1400 ELBRIDGE PAYNE RD STE 210, CHESTERFIELD, MO 63017-8520
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 8.11.2.1.2(a) | No | No | Machine room door has no self-closing, self-locking features. Repair | 3/12/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room door must be self closing and lockable. | 3/12/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work. | 9/2/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Fire extinguisher in machine room is expired, replace or have serviced. | 3/12/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room door shall be self closing / self locking | 3/12/2026 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work. Re-inspection required | 12/13/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Sump pump in pit is not working | 3/12/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency light is not working. Re-inspection required | 3/12/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room door shall be self closing & locking | 3/12/2026 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work. Re-inspection required | 3/12/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | Yes | No | Sump Pump in pit not working | 3/25/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency light is not working. Re-inspection required | 3/25/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | Yes | No | Machine room door shall be self closing & locking | 3/25/2026 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work. Re-inspection required | 3/25/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Inspection incomplete, need to perform the following tests to complete inspection: Could not perform relief pressure & 15 minute static test. Re-inspection required | 8/5/2026 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work. Re-inspection required | 8/5/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Fire extinguisher in machine room is expired, needs to be replaced or have serviced | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Elevator machine room door shall be self locking and self closing | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Elevator machine room lights do not work, need to repair lights | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | Yes | No | Relief pressure was only 220 psi. Test tag on control calve says 400 psi. Verify that elevator will pick the rated load with test weights and record full load working pressure and relief pressure. Re-inspection required | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work. Re-inspection required |