Inspection
Inspection Details
Equipment ID
506
506
Inspection Date
9/27/2022
9/27/2022
Inspection Type
Reinspection
Reinspection
Inspector Name
Christopher "RED" Staton
Christopher "RED" Staton
Mechanic Name
Shaun Deckard
Shaun Deckard
Relief Valve Pressure
.
.
Slide
Governor Rope Pull
Door Closing Force
.
.
External ID
ab09b686-2563-4c9b-b7de-9b29c0969de9
ab09b686-2563-4c9b-b7de-9b29c0969de9
Location
The Oaks Apartments
321 Hamilton St, Neosho, MO
Phone: (417) 451-5303
Email: NHA4321@AOL.com
321 Hamilton St, Neosho, MO
Phone: (417) 451-5303
Email: NHA4321@AOL.com
Owner
Attn: Neosho Housing Authority
Neosho Housing Authority
321 Hamilton St, Neosho, MO 64850
Phone: (000) 000-0000
Email: DirectorNeoshoHousing@outlook.com
Neosho Housing Authority
321 Hamilton St, Neosho, MO 64850
Phone: (000) 000-0000
Email: DirectorNeoshoHousing@outlook.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | Telephone not working--reinspect required | 8/30/2018 |
| conversion | conversion | n/a | No | No | no current certificate | 11/8/2018 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Remove empty oil buckets and used rags from Machine room | 8/6/2021 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Current State Operating Permit shall be displayed in the Equipment Room in a non-combustible frame. | 8/6/2021 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | I(1) Pit scavenger pump will be removed. (REINSPECTION within 30 days) | 8/6/2021 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Remove empty oil buckets and used rags from Machine room | 3/3/2021 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Current State Operating Permit shall be displayed in the Equipment Room in a non-combustible frame. | 3/3/2021 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | I(1) Pit scavenger pump will be removed. (REINSPECTION within 30 days) | 3/3/2021 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | phone shall work | 10/22/2021 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | repair water leak in machine room | 10/15/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | No MCP in machine room. | 10/15/2021 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | phone shall work | 10/22/2021 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | 2.27.1.1.6(a)Emergency communications loss monitor shall work. (REINSPECTION REQUIRED) | 9/27/2022 |