Inspection
Inspection Details
Equipment ID
14507
14507
Inspection Date
11/2/2022
11/2/2022
Inspection Type
Reinspection
Reinspection
Inspector Name
Raymond Stidham
Raymond Stidham
Mechanic Name
Relief Valve Pressure
520
520
Slide
Governor Rope Pull
Door Closing Force
20
20
External ID
ae1dfe95-ff82-4cca-9432-9cb10a869542
ae1dfe95-ff82-4cca-9432-9cb10a869542
Location
Nevada Regional Medical Center
800 S Ash St, Nevada, MO
Phone: (417) 667-3355
800 S Ash St, Nevada, MO
Phone: (417) 667-3355
Owner
Attn: Chad Boswell
Nevada Regional Medical Center
800 S Ash St, Nevada, MO 64772
Phone: (417) 448-3740
Email: cboswell@nrmchealth.com
Nevada Regional Medical Center
800 S Ash St, Nevada, MO 64772
Phone: (417) 448-3740
Email: cboswell@nrmchealth.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | needs record of oil loss | 2/21/2020 |
| conversion | conversion | n/a | No | No | needs maintance records on site | 2/21/2020 |
| conversion | conversion | n/a | No | No | pit shall be clean and dry-removal of any oil on floor | 2/21/2020 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | I-1 Mo -min--oil and debree in pit--pit needs to be cleaned | 2/21/2020 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | current certificate needs to be displayed | 2/21/2020 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | Pit needs to be cleaned--water/oil/debree | 3/23/2020 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Oil Accumulation in pit | 1/11/2024 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.4 Instructions for Locating Maintenance Records | No | No | No records | 1/11/2024 |
| A17.1-2016 : Elevators | 5.15 - Overspeed Valve | 8.6.5.16.5 | No | No | Must provide cat 5 test on or before next Annual insp. 8.6.5.16.5 | 1/23/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Must post current operating Cert. in Mach room 5.100(2) | 1/11/2024 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Must Make Emergency Phone Operable. 8.6.4.15 | 9/18/2025 |
| A17.1-2016 : Elevators | 2.36 - Hydraulic Cylinders | 8.6.5.5 Gland Packing and Seals | Yes | No | Must repair/replace jacke Packing gland to limit oil loss. (pit overflow bucket was full and had been emptied in the last 30 days.) 8.6.5.5 | 5/29/2026 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Pit must be kept free of oil. 8.6.4.7 | 5/29/2026 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Must make emergency phone operable. 8.6.4.15 |