Inspection
Inspection Details
Equipment ID
14509
14509
Inspection Date
11/2/2022
11/2/2022
Inspection Type
Reinspection
Reinspection
Inspector Name
Raymond Stidham
Raymond Stidham
Mechanic Name
Relief Valve Pressure
480
480
Slide
Governor Rope Pull
Door Closing Force
F=24/R=21
F=24/R=21
External ID
a267287f-8763-4959-b619-ada43209127e
a267287f-8763-4959-b619-ada43209127e
Location
Nevada Regional Medical Center
800 S Ash St, Nevada, MO
Phone: (417) 667-3355
800 S Ash St, Nevada, MO
Phone: (417) 667-3355
Owner
Attn: Chad Boswell
Nevada Regional Medical Center
800 S Ash St, Nevada, MO 64772
Phone: (417) 448-3740
Email: cboswell@nrmchealth.com
Nevada Regional Medical Center
800 S Ash St, Nevada, MO 64772
Phone: (417) 448-3740
Email: cboswell@nrmchealth.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | needs record of oil usage | 2/21/2020 |
| conversion | conversion | n/a | No | No | rear restrictor needs adjusted or repairerd | 2/21/2020 |
| conversion | conversion | n/a | No | No | needs maintance record on site | 2/21/2020 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7 | No | No | 8.11.3.1.1(f) emergency light needs battery | 2/21/2020 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | needs current certificarte posted | 2/21/2020 |
| A17.1-1996 : Elevators | 2.35 - Supply Line and Shutoff Valve | 303 | No | No | Shutoff valve in machine room will not close--needs replaced | 3/23/2020 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.4 Instructions for Locating Maintenance Records | No | No | No Records | 1/11/2024 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters’ Emergency Operation Documentation | No | No | Post monthly fire service log in machine room | 1/23/2024 |
| A17.1-2016 : Elevators | 5.15 - Overspeed Valve | 8.6.5.16.5 | No | No | Must perform Category 5 test on overspeed valve on or before next annual insp. 8.6.5.16.5 | 1/23/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Must post current operating Cert. in Mach Room 5.100(2) | 1/23/2024 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Must make Emergency Phone Operable. 8.6.4.15 | 9/18/2025 |
| A17.1-2016 : Elevators | 5.15 - Overspeed Valve | 8.6.5.16.5 | Yes | No | Must perform Cat. 5 Full load test/insp. for Overspeed Valve within next 90 days. 8.6.5.16.5 | 9/18/2025 |
| A17.1-2016 : Elevators | 2.36 - Hydraulic Cylinders | 8.6.5.5 Gland Packing and Seals | Yes | No | Must repair/replace Jack Packing Gland to limit oil loss. (5 gal pit bucket was full, noted it had been emptied in the last 45 days). 8.6.5.5 | 5/29/2026 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Pit must be kept free of Oil. 8.6.4.7 | 5/29/2026 |
| A17.1-2016 : Elevators | 2.36 - Hydraulic Cylinders | 8.6.5.5 Gland Packing and Seals | Yes | No | Must repace jack packing gland to limit oil loss. 8.6.5.5 | |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Pit must be kept free of oil. 5.1 | |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Must make emergency phone operable. 8.6.4.15 |