Inspection
Inspection Details
Equipment ID
21727
21727
Inspection Date
11/10/2022
11/10/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
David Folkert
David Folkert
Mechanic Name
Rodney Clay
Rodney Clay
Relief Valve Pressure
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
25/25
25/25
External ID
ea5632d8-3104-4528-b01e-9b1d7b38d524
ea5632d8-3104-4528-b01e-9b1d7b38d524
Location
Weigal Furniture Bldg Rehab
107 S 6TH ST, SAINT JOSEPH, MO
Phone: (816) 262-0637
107 S 6TH ST, SAINT JOSEPH, MO
Phone: (816) 262-0637
Owner
Attn: Rick Gilmore
Weigal Furniture Bldg Rehab
107 S 6th St, St. Joseph, MO 64506
Phone: (000) 000-0000
Weigal Furniture Bldg Rehab
107 S 6th St, St. Joseph, MO 64506
Phone: (000) 000-0000
Billing
Attn: Rick Gilmore
R&M Machinery
4601 S Lakewood Dr, St. Joseph, MO 64506
Phone: (000) 000-0000
Email: rgilmore@seamanschuske.com
R&M Machinery
4601 S Lakewood Dr, St. Joseph, MO 64506
Phone: (000) 000-0000
Email: rgilmore@seamanschuske.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Phone does not operate. | 11/9/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 8.6.4.11 | Yes | No | Need to shorten hoist ropes. Countweight buffer is fully compressed before top final limit actuates. | 4/30/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | No current state operating certificate on site. | 11/15/2021 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(b) | No | No | Provide written documentation of how to perform tests, and periodic inspections for installed equipment. Documentation to be kept inside the elevator control space. | 11/15/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | State operating certificate not displayed in control space | 2/28/2026 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.2(b)(5) | No | No | Written documentation of procedures to perform tests and periodic inspections need to be kept on site. | 2/28/2026 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.4.1(a)(1) | No | No | MRL not up to date | 2/28/2026 |
| A17.1-2016 : Elevators | 2.43 - Emergency Brake, Ascending Car Overspeed, and Unintended Car Movement Protection | 8.6.4.19.11 Ascending Overspeed Protection, Unintended Movement Devices, and Emg Brake | Yes | No | Test ascending car protection. | 11/29/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | state operating certificate not displayed | 2/28/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.7.2 Periodic Test Record (Test Tags) | No | No | Install 5 year test tag | 2/28/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.3.7 Phase 2 Operation Panel (Re-Inspection) | Yes | No | phase 2 both doors reopen on safety ray needs to bypass ray | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | car phone rang but not answered by anyone No communication was completed | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.11 Runby (Re-Inspection) | Yes | No | mfg run-by says max 2" sign mounted in pit stating same measured at 5-3/4" need to add stinger block |