Inspection
Inspection Details
Equipment ID
14594
14594
Inspection Date
10/24/2022
10/24/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
David Folkert
David Folkert
Mechanic Name
Jason Stout
Jason Stout
Relief Valve Pressure
480
480
Slide
Governor Rope Pull
Door Closing Force
26
26
External ID
3460d235-e1e3-49f9-a9f9-b66c51bf78a9
3460d235-e1e3-49f9-a9f9-b66c51bf78a9
Location
Heartland Regional- Medical Plaza 2
901 HEARTLAND RD, SAINT JOSEPH, MO
Phone: (816) 271-6406
901 HEARTLAND RD, SAINT JOSEPH, MO
Phone: (816) 271-6406
Owner
Attn: Bradley Connell
Mosaic Life Care
5325 Faraon St, St. Joseph, MO 64506
Phone: (816) 271-7539
Alt Phone: (816) 271-8876
Email: Bradley.Connell@mymlc.com
Mosaic Life Care
5325 Faraon St, St. Joseph, MO 64506
Phone: (816) 271-7539
Alt Phone: (816) 271-8876
Email: Bradley.Connell@mymlc.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state operating certificate inside machine | 11/1/2023 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | Pit light does not illuminate | 11/11/2023 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state operating certificate inside the machine room | 11/11/2023 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 | No | No | Pit light does not illuminate | 12/7/2023 |
| A17.1-2016 : Elevators | 2.5 - Housekeeping | 8.6.4.8 Machine Room and Machinery Space | No | No | Remove rags from machine room floor | 12/7/2023 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Clean pit | 12/7/2023 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.4.1(a)(1) | No | No | MRL not up to date | 12/7/2023 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | State operating certificate not displayed | 12/7/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Clean cartop | 12/7/2023 |
| A17.1-2016 : Elevators | 5.15 - Overspeed Valve | 8.6.5.16.5 | No | No | Perform overspeed valve test | 12/18/2023 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | State operating certificate not displayed | 12/18/2023 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Emergency power was not tested. | 11/22/2024 |