Inspection
Inspection Details
Equipment ID
18093
18093
Inspection Date
6/10/2022
6/10/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Christopher "RED" Staton
Christopher "RED" Staton
Mechanic Name
Shaun Deckard
Shaun Deckard
Relief Valve Pressure
470
470
Slide
Governor Rope Pull
Door Closing Force
20
20
External ID
9bdbbcd6-a5cd-45a7-b745-c996546410d7
9bdbbcd6-a5cd-45a7-b745-c996546410d7
Location
Carthage High School
2600 S River St, Carthage, MO
Phone: (000) 573-0010
Email: fleshert@carthagetigers.org
2600 S River St, Carthage, MO
Phone: (000) 573-0010
Email: fleshert@carthagetigers.org
Owner
Attn: Carthage R-9 School District
Carthage R-9 School District
709 W Centennial Ave, Carthage, MO 64836
Phone: (417) 359-7014
Email: fleshert@carthagetigers.org
Carthage R-9 School District
709 W Centennial Ave, Carthage, MO 64836
Phone: (417) 359-7014
Email: fleshert@carthagetigers.org
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.11.2.1.2(e) (Re-Inspection) | No | No | H-4 Mo Min non elevator items stored in machine room | 6/10/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | needs current certificate posted | 12/22/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.11.2.1.2(e) (Re-Inspection) | No | No | non elevator otems in the machine room | 6/10/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | 2-way communication device shall give proper location message, unresponsive on battery power (REINSPECTION REQUIRED) | 6/10/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | MCP shall be kept in equipment room, including Oil loss log and Fire service testing log, recorded monthly. | 1/5/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | Yes | No | : Emergency/auxiliary lighting shall work with power loss. (REINSPECTION REQUIRED) | 6/10/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit light fixture broken and hanging off wall. | 1/5/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.11.2.2.6 Fire Fighters Operation (Re-Inspection) | Yes | No | Phase 2 Keyswitch does not work. repair or replace. (REINSPECTION ReQUIRED) | 6/10/2022 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | 2021&2022VIO: H(4)/2.5/8.11.2.1.2(e). Non-elevator related items shall not be stored in Machine Room. | 12/22/2022 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | 2021&2022VIO: H(2) Machine room door shall be self-closing and self-locking. Closer broken | 12/22/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | 2021&2022VIO: G(1)/A17.1-2016:8.6.1.2.1(a)/2.40 Compliant/Required Documentation & MCP shall be kept in equipment room(neat/organized) including Wiring Diagrams, Oil log &Fire service log, recorded monthly | 12/22/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | 2021&2022VIO: I(6) Pit light fixture broken and hanging off wall. | 12/22/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean Pit. | 12/22/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | 2-way communication device shall give proper location message, unresponsive on battery power (REINSPECTION REQUIRED) | 6/10/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.11.2.2.6 | Yes | No | Phase 2 Keyswitch does not work. repair or replace. (REINSPECTION ReQUIRED) | 6/10/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | Yes | No | : Emergency/auxiliary lighting shall work with power loss. (REINSPECTION REQUIRED) | 6/10/2022 |