Inspection
Inspection Details
Equipment ID
15151
15151
Inspection Date
11/7/2022
11/7/2022
Inspection Type
Reinspection
Reinspection
Inspector Name
Michael Bailey
Michael Bailey
Mechanic Name
Adam Dragovich
Adam Dragovich
Relief Valve Pressure
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
na
na
External ID
125d9049-0bd3-40af-abf8-7f445d82fd3e
125d9049-0bd3-40af-abf8-7f445d82fd3e
Location
City Parc At Pines
1531 Pine St, St. Louis, MO
Phone: (317) 440-7788
1531 Pine St, St. Louis, MO
Phone: (317) 440-7788
Owner
Attn: City Parc at Pine
Plaza Square 50, LP c/o Sansone Group
120 S Central Ave Ste 500, St. Louis, MO 63105
Phone: (314) 336-3368
Email: kdurrwachter@sansonegroup.com
Plaza Square 50, LP c/o Sansone Group
120 S Central Ave Ste 500, St. Louis, MO 63105
Phone: (314) 336-3368
Email: kdurrwachter@sansonegroup.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Provide maintenance control program. | 8/13/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Clean the car top. | 3/16/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.7 Cleaning of Hoistway and Pit | No | No | Clean the pit. | 3/16/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The test is incomplete due to shutdown during test. Remaining items to test: light, bell, phone, buffers, unintended motion up/down. All weight portions, slide, runby. Building has emergency generator, determine if elevators operate on generator, if so, test. | 2/22/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Car operating panel shall have car number displayed. | 4/15/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.16 - Rated load, platform area, and data plate | 2.16.3.1 Capacity Plates | No | No | Car operating panel shall have car capacity displayed. | 4/15/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 2.14.7.1.2 Minimum Illumination | No | No | Cab lighting - All lamps shall work. | 4/15/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 2.7.3.4 | No | No | Machine room door shall be self-closing and self-locking and operable from the interior space without the use of a key. The lock is damaged. | 4/15/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | The pit shall be kept clean. Remove excess debris. | 4/15/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Car operating panel independent service switch is broken. | 4/15/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.23 - Suspension rope | 2.20 | No | No | Hoist ropes are showing moderate "rouge". Ropes shall be cleaned and lubricated per OEM recommendations. Monitor condition and diameter. | 4/15/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car, operating on emergency power, annually. | 4/12/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2.3 (Elevator Emergency Power Illuminated Signal) | No | No | Replace missing/damaged emergency power jewel in hall station. | 4/15/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | State operating certificate is expired. | 6/2/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.23 - Suspension rope | 8.11.2.1.3(cc) | Yes | No | Car ropes need to be replaced. | 5/22/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.8 Machine Rooms and Machinery Spaces | No | No | Machine room shall be kept clean and free of non-elevator materials. | 6/2/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | No | No | Monthly fire service testing log not filled out. | 6/2/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 3.26.10 (Auxiliary Power)(Re-Inspection) | Yes | No | Auxiliary battery lowering unit is not working. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.15 - sign and operating device symbols | 2.26.12 | No | No | Fire hat jewel shall be replaced. | 6/2/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.11.2.2.6 Fire Fighters Operation (Re-Inspection) | Yes | No | Fire service operation door shall be repaired. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Current MCP shall be kept in the machine room. | 6/2/2026 |