Inspection
Inspection Details
Equipment ID
2805
2805
Inspection Date
9/19/2018
9/19/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michial Linenfelser
Michial Linenfelser
Mechanic Name
Marcus Geno
Marcus Geno
Relief Valve Pressure
Slide
Governor Rope Pull
na
na
Door Closing Force
15
15
External ID
70286906-3f3f-4afd-98f0-c27db198aeff
70286906-3f3f-4afd-98f0-c27db198aeff
Location
SSM-St. Joseph Health Center
300 1ST CAPITOL DR, SAINT CHARLES, MO
300 1ST CAPITOL DR, SAINT CHARLES, MO
Owner
SSM St. Joseph Health Care
300 1ST CAPITOL DR, SAINT CHARLES, MO 63301-2844
300 1ST CAPITOL DR, SAINT CHARLES, MO 63301-2844
Billing
Attn: SSM St. Joseph Health Care
300 1ST CAPITOL DR, SAINT CHARLES, MO 63301-2844
300 1ST CAPITOL DR, SAINT CHARLES, MO 63301-2844
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 111.5 Restricted Opening of Hall/Car Doors | Yes | No | The car door restrictor device has been removed to restrict opening of the car doors to a maximum of 4 inches when the car is away from the landing zone. Provide a proper restrictor device to comply with code and passenger safety. | 10/4/2018 |
| A17.1-1996 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 111.5 Restricted Opening of Hall/Car Doors | Yes | No | The car door restrictor device shall be adjusted so that it will properly catch and restrict opening of the car doors to a maximum of 4 inches when the car is away from the landing zone. Reinspection is required. | 11/6/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Need to replace 2 top left counterweight guide rollers | 10/7/2025 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Hoist ropes are at minimum allowable diameter and shall be replaced within 60 days. Alteration permit and inspection required. Re-inspection required | 12/13/2024 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit needs to be cleaned | 10/7/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Provide & install test tag permanently marked with test data on all appropriate equipment. Re-inspection required | 12/13/2024 |
| A17.1-2016 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 8.6.4.13.1(l)(Door Restrictor) | Yes | No | The car door restrictor device shall be adjusted so that it will properly catch and restrict opening of the car doors to a maximum of 4 inches when the car is away from the landing zone. Re-inspection required | 12/13/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Replace 2 top left counterweight guide rollers | 10/7/2025 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Hoist ropes are at a minimum allowable diameter and shall be replaced within 60 days. Alteration permit and inspection required. Re-inspection required | 10/7/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.7.2 Periodic Test Record (Test Tags) | No | No | Provide and install test tags permanently marked with test data on all appropriate equipment | 10/7/2025 |