Inspection
Inspection Details
Equipment ID
2806
2806
Inspection Date
9/19/2018
9/19/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michial Linenfelser
Michial Linenfelser
Mechanic Name
Marcus Geno
Marcus Geno
Relief Valve Pressure
Slide
Governor Rope Pull
na
na
Door Closing Force
25
25
External ID
869a1813-954a-4325-8267-8e4d6e1d3595
869a1813-954a-4325-8267-8e4d6e1d3595
Location
SSM-St. Joseph Health Center
300 1ST CAPITOL DR, SAINT CHARLES, MO
300 1ST CAPITOL DR, SAINT CHARLES, MO
Owner
SSM St. Joseph Health Care
300 1ST CAPITOL DR, SAINT CHARLES, MO 63301-2844
300 1ST CAPITOL DR, SAINT CHARLES, MO 63301-2844
Billing
Attn: SSM St. Joseph Health Care
300 1ST CAPITOL DR, SAINT CHARLES, MO 63301-2844
300 1ST CAPITOL DR, SAINT CHARLES, MO 63301-2844
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (M) - Car Safeties and Speed Governors | (M)8 | x | x | Upon performing the required five year full load, the elevator safety governor was found to be worn to a degree that the mechanical and electrical protection devices would not activate within the required limits. Repair or replacement of the governor is required and a reinspection shall be performed before the elevator can be returned to service. | 1/3/2020 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | The testing has not been completed on the elevator at this time. The weight test shall be performed, safeties set, and buffers compressed before the inspection is completed. | 1/3/2020 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.2.5 Rope Tension (Re-Inspect) | x | The hoist rope tension is unequal due to the anti-rotational device being broken. Redistribute tension properly and repair anti-rotational device to maintain equal tension on all hoisting ropes. | 11/7/2024 | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | Pit needs to be cleaned | |||
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | Pit light is not working | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | Need to replace bottom right counterweight guide roller | |||
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | x | Hoist ropes are rouged and undersized. Need to aquire alteraion permit and replace ropes within 60 days and perform alteration inspection. Re-inspection required | 12/13/2024 | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Provide & install test tag permanently marked with test data on all appropriate equipment. Re-inspection required | 12/13/2024 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | The anti-rotational device on the counterweight fastening hitch for the hoist ropes is broken and shall be replaced to keep the hoist ropes from spinning. | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | The anti-rotational device on the counterweight fastening hitch for the hoist ropes is broken and shall be replaced to keep the hoist ropes from spinning | |||
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | Light in pit shall work | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | Replace the bottom right counterweight guide roller | |||
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | x | Hoist ropes are rouged and undersized. Acquire alteration permit and replace ropes within 60 days and perform alteration inspection. Re-inspection required | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.7.2 Periodic Test Record (Test Tags) | Provide and install test tags permanently marked with test data on all appropriate equipment |