Inspection
Inspection Details
Equipment ID
2854
2854
Inspection Date
9/18/2018
9/18/2018
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
David Folkert
David Folkert
Mechanic Name
Christopher Bolin
Christopher Bolin
Relief Valve Pressure
Slide
22 in
22 in
Governor Rope Pull
NA/450
NA/450
Door Closing Force
26
26
External ID
0cce33a4-80ed-4eab-8af2-05771c81a7ff
0cce33a4-80ed-4eab-8af2-05771c81a7ff
Location
US Bank- Robidoux Center
415 FRANCIS ST, SAINT JOSEPH, MO
415 FRANCIS ST, SAINT JOSEPH, MO
Owner
US Bank
3615 W BROADWAY BLVD, SEDALIA, MO 65301-2558
3615 W BROADWAY BLVD, SEDALIA, MO 65301-2558
Billing
Attn: US Bank Corporate Real Estate
3640 S NOLAND RD STE 201, INDEPENDENCE, MO 64055-3319
3640 S NOLAND RD STE 201, INDEPENDENCE, MO 64055-3319
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Car lighting is less than 5 ft candles of illumination. Need to provide adequate lighting inside the elevator. | 3/16/2021 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Need to test firefighters operation monthly and keep written record log inside machine room. | 3/16/2021 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Test and log firefighter operation monthly | 9/20/2022 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Elevator cab lighting is insufficient, less than 5 foot candles of illumination. | 9/20/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Braille plates next to car button #1, and on floor 1 entrance frame need a star on them to designate 1 as the main fire landing. Remove star on LL car button, and floor LL entrance frame. | 9/20/2022 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Remove firefighter call cancel button from car operating panel. Firefighter operation on this elevator was not designed for call cancel feature. | 8/31/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state operating certificate in the machine room. | 9/20/2022 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room access door needs to be self-locking | 9/20/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | State operating certificate not displayed in machine room | 9/20/2022 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | REPLACE BAD HOIST ROPES | 7/30/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | No | No | THE 110VAC BREAKER LABELED ELEVATOR #1 DID NOT REMOVE POWER. WE COULD NOT TEST EMERGENCY LIGHT AND ALARM | |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | REPLACE BAD HOIST ROPES | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | EMERGENCY PHONE NOT WORKING |