Inspection
Inspection Details
Equipment ID
11452
11452
Inspection Date
10/28/2022
10/28/2022
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Bradley Rasnake
Bradley Rasnake
Mechanic Name
Jeff Setchfield
Jeff Setchfield
Relief Valve Pressure
Slide
11
11
Governor Rope Pull
225 / 750
225 / 750
Door Closing Force
17
17
External ID
9fab345f-9b2e-44db-9fe9-d8d6d16d9579
9fab345f-9b2e-44db-9fe9-d8d6d16d9579
Location
Bevo Bottling Plant- Bldg #137
619 ARSENAL ST, SAINT LOUIS, MO
Phone: (314) 256-6278
619 ARSENAL ST, SAINT LOUIS, MO
Phone: (314) 256-6278
Owner
Attn: 137-2
Anheuser Busch
1 Busch Pl, St. Louis, MO 63118
Phone: (314) 577-3998
Email: ryan.brohammer@anheuser-busch.com
Anheuser Busch
1 Busch Pl, St. Louis, MO 63118
Phone: (314) 577-3998
Email: ryan.brohammer@anheuser-busch.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Shorten hoist ropes, negative cwt. runby and adjust tension between ropes. | 3/14/2019 |
| conversion | conversion | n/a | No | No | Replace interlock box cover at level 5. | 3/14/2019 |
| conversion | conversion | n/a | No | No | Replace cap bolt on pick-up roller at level 4. | 3/14/2019 |
| conversion | conversion | n/a | No | No | Replace sight guard on right hoistway door at level B. | 3/14/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.28 - Counterweight and counterweight buffer | 2.21 | No | No | Repair or replace counterweight sheave. Rope imprinting sheave groove. | 9/26/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Water in the pit. | 9/26/2025 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | Yes | Suspension ropes are severely undersized with rouge. Red tagged, Re-inspection required | 10/28/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Right car top sheave bearing is going out causing a popping sound. Sheave tracks are also worn down causing ropes to sink into sheave grooves. | 9/26/2025 |
| MO Minimum : Elevators | (A) - Hoistways | (A)3 | No | No | There are numerous missing Fire tabs throughout hoistway, need to be replaced. | 9/26/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | The main traction sheave tracks are worn down causing the ropes to sink into sheave grooves. | 9/26/2025 |
| MO Minimum : Elevators | (A) - Hoistways | (A)3 | No | No | There are numerous fire tabs on hoistway doors missing | 9/26/2025 |
| A17.1-2016 : Elevators | 3.17 - Door and gate equipment | 8.6.4.13 | No | No | Hoistway door panels shall have 2 gibs mounted on the bottom of each panel | 9/26/2025 |
| MO Minimum : Elevators | (A) - Hoistways | (A)3 | No | No | There are numerous fire tabs on hoistway doors missing | 9/26/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.17 - Door and gate equipment | 8.6.4.13 Door Systems | Yes | No | Basement hoistway doors shall be adjusted so that they are closed at the bottom of the door. Re-inspection required | 9/26/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.7 - Car door or gate | 2.14.5 | No | No | Car doors open too far and create a shear and pinch point. | 9/26/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | Yes | No | Car top sheave bearings noisy, replace. |