Inspection
Inspection Details
Equipment ID
14582
14582
Inspection Date
9/17/2018
9/17/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Tim Crafton
Tim Crafton
Mechanic Name
Alex Brinkman
Alex Brinkman
Relief Valve Pressure
Slide
Governor Rope Pull
45/420
45/420
Door Closing Force
22
22
External ID
ffc28f37-3d4a-436b-bcf1-8ea3c8f26b59
ffc28f37-3d4a-436b-bcf1-8ea3c8f26b59
Location
The Lofts @ 2020 Washington
2020 WASHINGTON AVE, SAINT LOUIS, MO
2020 WASHINGTON AVE, SAINT LOUIS, MO
Owner
Lofts @ 2020 Washington Condo Assoc
2020 WASHINGTON AVE UNIT 710, SAINT LOUIS, MO 63103-1653
2020 WASHINGTON AVE UNIT 710, SAINT LOUIS, MO 63103-1653
Billing
Attn: Rafco Properties
7700 FORSYTH BLVD STE 100, CLAYTON, MO 63105-1838
7700 FORSYTH BLVD STE 100, CLAYTON, MO 63105-1838
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit shall be clean & dry. Pit has 10" of water in it | |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit light shall be made operable | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Phone in elevator cab does not work. Re-inspection required | 1/14/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Fire extinguisher is overdue for annual maintenance, need to have serviced or replaced. | |
| MO Minimum : Elevators | (I) - Pits | (I)2 | Yes | Yes | One of the car spring buffers was laying on its side in the elevator pit. All buffer stands and buffer springs are severly rusted out. Need to replace all buffer stands & buffer springs. Elevator Red-tagged and removed from service. Re-inspection required | 1/14/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)5 | No | No | Elevator pit ladder is loose due to bottom support being rusted off, repair or replace pit ladder | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Phone in elevator cab still does not work, possible phone line problem. Re-inspection required | 4/10/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)3 | No | No | Fire extinguisher is overdue for annual maintenance, need to perform maintenance on fire extinguisher. | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current operating certificate shall be displayed in the machine room | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Fire extinguisher is expired in machine room, have serviced or replaced | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Fire extinguisher in the machine room is expired, have serviced or replaced |