Inspection
Inspection Details
Equipment ID
14583
14583
Inspection Date
9/17/2018
9/17/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Tim Crafton
Tim Crafton
Mechanic Name
Alex Brinkman
Alex Brinkman
Relief Valve Pressure
Slide
Governor Rope Pull
45/590
45/590
Door Closing Force
25
25
External ID
959a66e3-b72e-4e32-b6a9-14cbd9b31438
959a66e3-b72e-4e32-b6a9-14cbd9b31438
Location
The Lofts @ 2020 Washington
2020 WASHINGTON AVE, SAINT LOUIS, MO
2020 WASHINGTON AVE, SAINT LOUIS, MO
Owner
Lofts @ 2020 Washington Condo Assoc
2020 WASHINGTON AVE UNIT 710, SAINT LOUIS, MO 63103-1653
2020 WASHINGTON AVE UNIT 710, SAINT LOUIS, MO 63103-1653
Billing
Attn: Rafco Properties
7700 FORSYTH BLVD STE 100, CLAYTON, MO 63105-1838
7700 FORSYTH BLVD STE 100, CLAYTON, MO 63105-1838
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit shall be clean & dry, pit has 10" of water in it | |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit light is not working, needs repair | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Elevator cab phone does not work. Re-inspection required | 2/17/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | |
| MO Minimum : Elevators | (I) - Pits | (I)2 | Yes | No | All buffer stands & buffer springs in elevator pit are rusted, need to replace all buffer stands & buffer springs in elevator pit. Re-inspection required | 2/17/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Need to test car safeties with rated load at rated speed. Re-inspection required | 2/17/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Need to perform 125% of rated brake test. Re-inspection required | 2/17/2025 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Elevator phone does not work, possible phone line problem, needs repaired. Re-inspection required | 2/17/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Need to test car safeties with rated load at rated speed. Re-inspection required | 2/17/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Need to perform 125% of rated load brake test. Re-inspection required | 2/17/2025 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Elevator cab phone does not work, possible phone line issue, needs repaired. Re-inspection required | 4/10/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room |