Inspection
Inspection Details
Equipment ID
13419
13419
Inspection Date
11/17/2022
11/17/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Gallaher
Michael Gallaher
Mechanic Name
Brant Willtrout
Brant Willtrout
Relief Valve Pressure
385
385
Slide
Governor Rope Pull
Door Closing Force
21
21
External ID
f598085c-8901-4f02-ac24-12a4d02af192
f598085c-8901-4f02-ac24-12a4d02af192
Location
10th & Lami
1000 Lami St, St. Louis, MO
Phone: (314) 535-1919
1000 Lami St, St. Louis, MO
Phone: (314) 535-1919
Owner
Attn: 10th& Lami Inc
10th& Lami Inc
1000 LAMI ST, SAINT LOUIS, MO 63104
Phone: (000) 000-0000
10th& Lami Inc
1000 LAMI ST, SAINT LOUIS, MO 63104
Phone: (000) 000-0000
Billing
Attn: Interfaith Residence
Interfaith Residence
4385 MARYLAND AVE, SAINT LOUIS, MO 63108
Phone: (000) 000-0000
Email: hljohnson@doorwayshousing.org
Interfaith Residence
4385 MARYLAND AVE, SAINT LOUIS, MO 63108
Phone: (000) 000-0000
Email: hljohnson@doorwayshousing.org
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | Fire service key switch bezels not readable in car and hallway | 2/19/2019 | ||
| conversion | conversion | conversion - reinspect | Emergency phone not working | 1/31/2019 | ||
| conversion | conversion | n/a | Clean pit of debris | 2/19/2019 | ||
| conversion | conversion | n/a | Repair or replace electric eyes | 2/19/2019 | ||
| conversion | conversion | n/a | Do not use machine room as storage space | 2/19/2019 | ||
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Display current operating certificate in machine room. | 2/19/2019 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | Light rays are not working, mechanical edge works. Repair/replace light rays. Re-inspection required | 11/24/2022 | ||
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | x | Emergency phone is not working, needs repaired. Re-inspection required | 1/23/2024 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | x | Re-inspection to check door re-opening device (light ray), still not working, needs repaired. Re-inspection required | 1/23/2024 | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | x | Elevator cab phone is still not working. Re-inspection required | 1/23/2024 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | x | Door reopening device (light ray) does not work, needs repaired. Re-inspection required | 5/7/2024 | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | x | Phone in elevator cab does not work. Re-inspection required | 5/7/2024 | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Car failed 15 minute stand test, tech determined leaking back through the valve. Repair or replace as needed. | 11/25/2025 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | Provide means to collect oil scavenged, return line into tank to be removed.(due to extreme depth of pit, place bucket in machine room) | 11/25/2025 | ||
| A17.1-2016 : Elevators | 2.32 - Control Valve | 8.6.5.5.1 Examination and Maintenance | Oil is leaking back through the valve. Valve shall be repaired or replaced. | 12/16/2025 |