Inspection
Inspection Details
Equipment ID
21453
21453
Inspection Date
11/21/2022
11/21/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Thomas McGrath
Thomas McGrath
Mechanic Name
Richard King
Richard King
Relief Valve Pressure
600
600
Slide
Governor Rope Pull
Door Closing Force
Front 20 Rear 18
Front 20 Rear 18
External ID
c90b0e2f-010c-47f2-9e41-4d039db68df3
c90b0e2f-010c-47f2-9e41-4d039db68df3
Location
Fairfield Inn and Suites
130 Crossroads South Dr, Wentzville, MO
Phone: (417) 883-1204
130 Crossroads South Dr, Wentzville, MO
Phone: (417) 883-1204
Owner
Attn: Fairfield Inn Wentzville
Midas Wentzville, LLC
1804 Borman Circle Drive, Ste 100, St. Louis, MO 63146
Phone: (314) 764-4262
Email: kprainito@midashospitality.com
Midas Wentzville, LLC
1804 Borman Circle Drive, Ste 100, St. Louis, MO 63146
Phone: (314) 764-4262
Email: kprainito@midashospitality.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.36 - Hydraulic Cylinders | 3.18.3 | Yes | No | Jack seal leaking, needs to be replaced. | 12/9/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Clean pit of dirt and oil. | 3/19/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.2-2.27.8 | Yes | Yes | Door close button shall work on car fire service recall. Did NOT red tag the elevator. | 12/9/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | clean jack dip pans in pit | 1/8/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | No | No | Provide monthly fire service test & document on log posted in machine room | 1/8/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | REpair phone in car | 1/7/2020 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean drip pans in pit | 2/17/2022 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.11.3.1.5(a) | No | No | Remove oil from pit floor 2.2.2.3 | 12/21/2022 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.11.3.1.5(a) | No | No | Empty Drip pans in the pit 2.2.2.3 | 12/21/2022 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Perform monthly fire service test and document on log in machine room 1206.3 | 12/21/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Remove oil from pit floor. Written up on last inspection and still not completed 30 day maximum | 12/18/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.1 Examination and Maintenance | No | No | Empty drip pans in pit was written up last inspection and still not completed 30 day maximum | 12/18/2023 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Battery lowering unit not working maximum 30 days | 12/19/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergemcy comminication/phone not working maximum 30 days | 12/19/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Empty drip pans and oil oil from pit floor | 1/20/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | Seal and tag overspeed valve which was tested 11/15/23 | 1/20/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.36 - Hydraulic Cylinders | 3.18.3 | Yes | No | Packing needs relaced and clean oil from catch pans. | 3/15/2026 |