Inspection
Inspection Details
Equipment ID
22804
22804
Inspection Date
11/4/2022
11/4/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Gregory Sacks
Gregory Sacks
Mechanic Name
Jeffrey Miller
Jeffrey Miller
Relief Valve Pressure
605
605
Slide
Governor Rope Pull
Door Closing Force
21
21
External ID
4b3a467c-e611-433c-b26f-4db4651e68bc
4b3a467c-e611-433c-b26f-4db4651e68bc
Location
The Range
14803 Manchester Rd, Ballwin, MO
Phone: (636) 220-1300
14803 Manchester Rd, Ballwin, MO
Phone: (636) 220-1300
Owner
Attn: Sentinal Arms dba The Range - St. Louis West
Sentinal Arms dba The Range - St. Louis West
14803 MANCHESTER RD, BALLWIN, MO 63011
Phone: (636) 220-1300
Email: JHenderson@therangestl.com
Sentinal Arms dba The Range - St. Louis West
14803 MANCHESTER RD, BALLWIN, MO 63011
Phone: (636) 220-1300
Email: JHenderson@therangestl.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.35 - Supply Line and Shutoff Valve | 3.19.4.1 | No | No | The oil line shutoff shall be accessible from outside the hoistway. - Re-Inspection Required | 6/19/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.32 - Control Valve | 3.19.4.4 | No | No | Manual lowering shall be accessible from outside the hoistway. - Re-Inspection Required | 6/19/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.32 - Control Valve | 3.19.4.5 | No | No | Pressure gauge shall be accessible from outside the hoistway. - Re-Inspection Required | 6/19/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.37 - Pressure Switch | 3.26.8 Pressure Switch | Yes | No | Positive pressure switch is required as per 3.26.8 | 8/7/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 3.4 | Yes | No | The hoistway pit refuge space area is to be clearly and permanently marked and identified as "Refuge Space" and shall visible from the hoistway and entrance to the pit as required by the Missouri elevator safety board. | 8/7/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 3.4 | Yes | No | A sign with the words, "Danger Low Clearance," including the actual clearance dimension, shall be permanently posted on the power unit and shall be visible from within the pit and entrance to the pit as required by 3.4.1.6 and the Missouri elevator safety board. | 8/7/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 3.4 | Yes | No | Landing blocks and pipe stands shall be stored in the pit according to 8.6.4.7.2. | 8/7/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Maintenance control program shall be in place. | 8/4/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | Yes | No | The in car emergency lighting shall be operational. | 4/19/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an overspeed valve that is unsealed. A category 5 test shall be performed on the valve on or before the next annual inspection. | 11/21/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | The MCP shall not be stored on the top of the car. | 11/21/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The emegency phone shall establish 2-way communication. | 12/30/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The emergency phone shall establish two-way communication. | 3/23/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | Yes | The emergnecy phone shall establish 2-way communication. | 3/12/2026 |