Inspection
Inspection Details
Equipment ID
17677
17677
Inspection Date
11/22/2022
11/22/2022
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Paul Karrenbrock
Paul Karrenbrock
Mechanic Name
Jake Brennan
Jake Brennan
Relief Valve Pressure
Slide
18
18
Governor Rope Pull
50 / 150
50 / 150
Door Closing Force
27 / 28
27 / 28
External ID
699620b6-2ead-42c3-b671-f4e68cab17e7
699620b6-2ead-42c3-b671-f4e68cab17e7
Location
Park East Tower
4909 Laclede Ave, St. Louis, MO
Phone: (314) 361-3242
4909 Laclede Ave, St. Louis, MO
Phone: (314) 361-3242
Owner
Attn: Park East Tower
Park East Tower Association
4909 Laclede Ave, St. Louis, MO 63108
Phone: (314) 361-3242
Email: tom.parkeasttower@gmail.com
Park East Tower Association
4909 Laclede Ave, St. Louis, MO 63108
Phone: (314) 361-3242
Email: tom.parkeasttower@gmail.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | 4. The movement of the car initiated and maintained by the access switch at the lowest landing shall be limited in the up direction to the point where the bottom of the platform guard is even with hoistway entrance header. The elevator will not run back down after it?s been ran up to its limit. | 10/25/2018 |
| conversion | conversion | conversion - reinspect | Yes | No | 5. All inspections and testing required shall be made in accordance with the standards established by these rules and regulations. Inspection and testing was not completed. | 1/31/2018 |
| conversion | conversion | conversion - reinspect | Yes | No | 1. Maintenance records shall document compliance with 8.6 of the Code and shall include records, with a description of maintenance task performed and dates. No entries since Oct. 2016 and no digital records could be provided at the time of inspection, meeting code requirements. | 1/31/2018 |
| conversion | conversion | n/a | No | No | 2. Hoistways and pits shall be kept free of dirt and rubbish and shall not be used for storage purposes. The pit needs to be cleaned. | 10/25/2018 |
| conversion | conversion | conversion - reinspect | Yes | No | 3. Firefighters? emergency operation shall be tested to determine conformance with the applicable requirements. Firefighter?s emergency operation not tested. | 1/31/2018 |
| conversion | conversion | n/a | No | No | 1. Maintenance records shall document compliance with 8.6 of the Code and shall include records, with a description of maintenance task performed and dates. No entries since Oct. 2016 and no digital records could be provided at the time of inspection, meeting code requirements. | 10/25/2018 |
| conversion | conversion | n/a | No | No | 4. When the counterweight displacement switch is activated, the elevator, if in motion, shall initiate an emergency stop and then proceed away from the counterweight at a speed of not more than 150 ft/min to the nearest available floor, open the doors, and shut down. The counterweight displacement switch is activated by two wires running the length of the hoistway; the one on the left side does not function. When shorted the elevator does not cause displacement switch to activate. | 10/25/2018 |
| conversion | conversion | n/a | No | No | 2. Hoistways and pits shall be kept free of dirt and rubbish and shall not be used for storage purposes. The pit needs to be cleaned. | 10/25/2018 |
| conversion | conversion | n/a | No | No | 3. The movement of the car initiated and maintained by the access switch at the lowest landing shall be limited in the up direction to the point where the bottom of the platform guard is even with hoistway entrance header. The elevator will not run back down after it?s been ran up to its limit. | 10/25/2018 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(d) | No | No | 1) A written Maintenance Control Program shall be in place to maintain the equipment in compliance with the requirements of Section 8.6. Ref: 8.6.1.2.1 | 11/10/2020 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | 2) Hoistways and pits shall be kept free of dirt and rubbish and shall not be used for storage purposes. Pit needs to be cleaned. Ref: 8.6.4.7.1 | 11/10/2020 |
| A17.1-2016 : Elevators | 3.23 - Suspension Means | 8.11.2.1.3(cc) | No | No | 3) Suspension means (Item 3.23) shall be inspected and replaced as specified in ASME A17.6. Rouge is showing in all the ropes making some under sized. Re-inspect Ref: 8.11.2.1.3(cc) 60 days to replace or Red Tag. | 11/10/2020 |