Inspection
Inspection Details
Equipment ID
17853
17853
Inspection Date
9/24/2018
9/24/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Ronald Edwards
Ronald Edwards
Mechanic Name
Relief Valve Pressure
Slide
Governor Rope Pull
N/a
N/a
Door Closing Force
20
20
External ID
914a1267-10f7-4f1a-bca4-8310887fc0a1
914a1267-10f7-4f1a-bca4-8310887fc0a1
Location
Independence Regional Health Center
19600 E 39TH ST S, INDEPENDENCE, MO
19600 E 39TH ST S, INDEPENDENCE, MO
Owner
Center Point Medical Center
19600 E 39TH ST S, INDEPENDENCE, MO 64057-2301
19600 E 39TH ST S, INDEPENDENCE, MO 64057-2301
Billing
Attn: Independence Regional Health Center
19600 E 39TH ST S, INDEPENDENCE, MO 64057-2301
19600 E 39TH ST S, INDEPENDENCE, MO 64057-2301
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | no records of any kind on site | 2/27/2023 | ||
| A17.1-2016 : Elevators | 2.17 - Drive machine brake | 8.7.2.25.1 | new mach no rope gripper | 2/25/2021 | ||
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | couldnt run emg. power test at time of insp. | 2/25/2021 | ||
| A17.1-2016 : Elevators | 2.16 - Overhead Beam and Fastenings | 8.7.2.9 | no report from licensed prof. eng.on support for new floor an mach. beams | 2/27/2023 | ||
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | standby power didnt work properly | 2/25/2021 | ||
| A17.1-2016 : Elevators | 2.17 - Drive machine brake | 8.7.2.25.1 | no rope gripper or emg. brake | 2/25/2021 | ||
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | no mcp on site | 2/27/2023 | ||
| A17.1-2016 : Elevators | 2.16 - Overhead Beam and Fastenings | 8.7.2.9 | no report on mach.room floor over hoistway by prof. eng. | 2/27/2023 | ||
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | no current cirt. displayed | 6/24/2024 | ||
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | x | Emg power couldnt be tested at this time scheduled for april | 2/27/2023 | |
| A17.1-2016 : Elevators | 2.16 - Overhead Beam and Fastenings | 8.7.2.9 | no eng. study done on mach. room floor done by prof. eng. | 6/24/2024 | ||
| A17.1-2016 : Elevators | 2.17 - Drive machine brake | 8.7.2.25.1 | x | no emg. brake installed as per code | 2/27/2023 | |
| A17.1-2016 : Elevators | 4.1 - Car platform guard | 2.15.9 | platform guards need to be 48 ins. with emg brake | 6/12/2024 | ||
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | current operatig cirt not displayed | 3/6/2024 | ||
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | no current cirt displayed | 6/24/2024 | ||
| A17.1-2016 : Elevators | 4.1 - Car platform guard | 2.15.9 | need to have a 48 in platform guard or a variance | 6/12/2024 | ||
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.5.14.3(f) | x | couldnt run emg power test at time of insp | 3/6/2024 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 8.6.4.11 | x | Zero counterweight runby, shorten ropes. |