Inspection
Inspection Details
Equipment ID
8838
8838
Inspection Date
11/16/2022
11/16/2022
Inspection Type
Reinspection
Reinspection
Inspector Name
Robert Kehm
Robert Kehm
Mechanic Name
David Howerton
David Howerton
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
9c371bee-395c-4522-a330-64f8a6ba29bc
9c371bee-395c-4522-a330-64f8a6ba29bc
Location
Gallery 720
720 Olive St, St. Louis, MO
Phone: (314) 436-1711
720 Olive St, St. Louis, MO
Phone: (314) 436-1711
Owner
Attn: Brandonview LLC
Brandonview LLC
720 Olive St, Apt 2720, St. Louis, MO 63101
Phone: (314) 436-1711
Fax: (314) 436-7348
Email: mgummels@stlluxury.com
Brandonview LLC
720 Olive St, Apt 2720, St. Louis, MO 63101
Phone: (314) 436-1711
Fax: (314) 436-7348
Email: mgummels@stlluxury.com
Billing
Attn: Brandonview LLC
Brandonview LLC
720 Olive St, Apt 2720, St. Louis, MO 63101
Phone: (314) 436-1711
Fax: (314) 436-7348
Email: gallery720@stlluxury.com
Brandonview LLC
720 Olive St, Apt 2720, St. Louis, MO 63101
Phone: (314) 436-1711
Fax: (314) 436-7348
Email: gallery720@stlluxury.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.12 - Pipes, wiring, and ducts | 2.8 | x | Install cover on the car top control box. | 6/28/2022 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.12 - Pipes, wiring, and ducts | 2.8 | x | Install duct covers on wire raceway at top of hoistway. | 6/28/2022 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.3 - Operating control devices | 2.26.1.1 | x | Properly secure the car operating panel. | 6/28/2022 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.10 - Compensating chains, ropes, and sheaves | 8.11.2.1.5(h) | x | Compensation ropes shall be equally tensioned. | 6/28/2022 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.12 - Pipes, wiring, and ducts | 2.8 | x | The tape switch electrical box shall have a cover installed. | 6/28/2022 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.12 - Pipes, wiring, and ducts | 2.8 | x | Unused wire raceway and junction box shall be removed from the hoistway. | 6/28/2022 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.8 - Car safeties and guiding members - including roped-hydraulic elevators installed under A17.1b-1989 and later editions | 8.11.2.1.5(j) | x | The car safeties shall be tested. | 6/28/2022 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.14 - Code data plate | 8.9 | x | Provide a code compliant code data tag. | 6/28/2022 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 2.7.3.4 | x | The machine room door shall be self-closing and self-locking. | 6/28/2022 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | x | Provide a code compliant MCP including onsite documents. | 6/28/2022 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.9 - Buffers and emergency terminal speed limiting devices | 8.10.2.2.5(c) | x | Car and counterweight buffers shall be tested. | 6/28/2022 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.23 - Suspension rope | 8.7.2.21 | x | All hoist rope sheave guards shall be checked and adjusted for proper operation. | 6/28/2022 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.23 - Suspension rope | 2.18.7 | x | Install hoist rope data tag. | 6/28/2022 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.11.2.2.6 Fire Fighters Operation (Re-Inspection) | x | Phase 1 fire service shall be tested, as well as, all initiating devices. | 6/28/2022 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.8 - Door closing force | 8.11.2.1.1(h) | x | Door closing force shall be tested. | 6/28/2022 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.15 - sign and operating device symbols | 8.11.2.1.1(o) | x | Patch holes where prior direction arrows were located on various floors. | 6/28/2022 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.9 - Buffers and emergency terminal speed limiting devices | 8.10.2.2.5(c) | x | Counterweight comp rope bracket shall not contact comp sheave when counterweight buffer is fully compressed. | 6/28/2022 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | Patch holes where prior directional arrows were located on various floors. | 11/18/2025 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.12 - Pipes, wiring, and ducts | 2.8 | Remove unused junction box in the hoistway. | 11/18/2025 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | If the emergency communication means is normally connected to the building power supply, it shall automatically transfer to a source of standby or emergency power as required by the applicable building code. The power source shall be capable of providing for illumination of the visual indication within the car, and the means of emergency communications for at least 4 hours; and the audible signaling device for at least 1 hour. | 11/16/2022 | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current operating certificate shall be displayed in machine room. | 11/18/2025 |