Inspection
Inspection Details
Equipment ID
10214
10214
Inspection Date
12/5/2022
12/5/2022
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Michial Linenfelser
Michial Linenfelser
Mechanic Name
David Howerton
David Howerton
Relief Valve Pressure
480
480
Slide
Governor Rope Pull
Door Closing Force
12
12
External ID
ad978f0d-84e5-46a2-86d4-7f9665f19b20
ad978f0d-84e5-46a2-86d4-7f9665f19b20
Location
Social Security Building
717 N 16th St, St. Louis, MO
Phone: (888) 748-2014
717 N 16th St, St. Louis, MO
Phone: (888) 748-2014
Owner
Attn: 701 N 16th Street, LLC
701 N 16th Street, LLC
10000 Watson Rd, Ste 1L5, St. Louis, MO 63126
Phone: (314) 822-1790
Email: crestwoodmed@sbcglobal.net
701 N 16th Street, LLC
10000 Watson Rd, Ste 1L5, St. Louis, MO 63126
Phone: (314) 822-1790
Email: crestwoodmed@sbcglobal.net
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency alarm bell does not work. | 6/25/2020 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | Yes | No | Emergency light does not work. | 6/25/2020 |
| A17.1-1996 : Elevators | 3.12 - Pipes, wiring, and ducts | 1001.2(c)(18) | No | No | Smokes and heat box is missing wire cover. | 2/4/2023 |
| A17.1-2016 : Elevators | 5.15.2 Unsealed Overspeed Valve | 8.6.5.16.5 (Re-Inspect) | Yes | No | OSV test due in 30 days | 12/5/2022 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Not less than two lamps or sets of lamps of equal illumination shall be provided. | 2/4/2023 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | No | No | A written MCP shall be in place to maintain the equipment in compliance with state requirements | 2/4/2023 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7 | No | No | The cab ceiling is of the open egg-crate type, which does not provide protection from the light bulbs should they shatter. The lights shall be guarded by plastic sleeve or some other means to properly protect passengers. | 8/8/2023 |
| A17.1-1996 : Elevators | 2.4 - Machine space | 101.1a | No | No | Ceiling tiles have been removed in the machine room, the ceiling tiles shall be reinstalled to maintain the fire resistance rating of the machine room. | 8/8/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) | Yes | No | This elevator has an overspeed valve device installed that is now required to have a 5 year full load test performed. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Overspeed valve shall be tested within the next 30 days, this is the second notice. | 3/22/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The 5 year annual test has not been completed, the overspeed valve shall be tested. | 3/22/2023 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | The cab ceiling is of the egg-crate type, which does nor provide protection from the light bulbs should they shatter. The lights shall be guarded by plastic sleeve or some other means to properly protect passengers | 8/8/2023 |
| A17.1-1996 : Elevators | 2.4 - Machine space | 101.1a | No | No | Ceiling tiles have been removed in the machine room, the ceiling tiles shall be reinstalled to maintain fire resistance rating of the machine room | 8/8/2023 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work. | 2/7/2024 |