Inspection
Inspection Details
Equipment ID
20627
20627
Inspection Date
7/31/2018
7/31/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
John Hambrough
John Hambrough
Relief Valve Pressure
Slide
Governor Rope Pull
N/A
N/A
Door Closing Force
22
22
External ID
7764f4f6-c1cc-4d97-8f3f-42aa8db708a5
7764f4f6-c1cc-4d97-8f3f-42aa8db708a5
Location
TLG Beaux Arts, LLC
711 N GRAND BLVD, SAINT LOUIS, MO
711 N GRAND BLVD, SAINT LOUIS, MO
Owner
TLG Beaux Arts, LLC
319 N 4TH ST STE 1000, SAINT LOUIS, MO 63102-1937
319 N 4TH ST STE 1000, SAINT LOUIS, MO 63102-1937
Billing
Attn: TLG Beaux Arts, LLC
319 N 4TH ST STE 1000, SAINT LOUIS, MO 63102-1937
319 N 4TH ST STE 1000, SAINT LOUIS, MO 63102-1937
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.9 Cleaning of Car Tops | No | No | Clean the car top. The car top shall be kept clean. | 11/9/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2 Design and Construction of Pits | No | No | Clean the pit. The pit shall be kept clean. | 11/9/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 1/24/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 2/6/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 4/16/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.9 Cleaning of Car Tops | No | No | The car top shall be cleaned. | 4/16/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.6 - Governor-rope tension devices | 2.18.7 | Yes | No | Governor rope shall be shortened/replaced to allow proper tension device clearance (approx 1" from touching the pit floor). | 10/3/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required shall be provided in the machine room. Fire service testing shall be documented monthly. | 4/16/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room. | 4/16/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.1.1(q) | Yes | No | Emergency power operations must be tested within 30 days. | 3/26/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.9 Cleaning of Car Tops | No | No | Top of cars shall be kept free of oil, water, dirt and rubbish. | 2/9/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.7 Cleaning of Hoistways and Pits | No | No | Pits shall be kept free of dirt and rubbish. | 2/9/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.8 Machine Rooms and Machinery Spaces | No | No | There is "Black Mold" in the machine room on the wall constructed of drywall alongside the drive machine and governor, opposite from the controller. Steps must be taken to midigate, remove mold, and repair source of moisture that is causing mold to form. | 2/9/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.8 Machine Rooms and Machinery Spaces | No | No | There is "Black Mold" in the machine room on the wall constructed of drywall alongside the drive machine and governor, opposite from the controller. Steps must be taken to midigate, remove mold, and repair source of moisture that is causing mold to form. | 2/9/2026 |