Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No Emergency communication inoperable. Re-inspection required 2/8/2023
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting No No Emergency car lighting is not operational, likely indicating that the back up power device has failed, needs repair 2/8/2023
MO Minimum : Elevators (I) - Pits (I)1 No No The liquid in the pit needs to be cleaned out 10/10/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Emergency phone not working. 12/4/2018
A17.1-2016 : Elevators 5.15 - Overspeed Valve 8.6.5.16.5 No No Must have an OSV test in 30 days 12/10/2021