MO Minimum : Elevators
|
(A) - Hoistways
|
(A)16
|
|
|
NEC - The sump pump shall have a maximum cord length of 6 feet.
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
In cab emergency telephone shall work.
|
9/21/2018
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
The in car emergency telephone shall be operational.
|
7/22/2019
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
|
1/4/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
|
|
An acceptance test tag is required.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
The in car emergency telephone shall be operational.
|
1/19/2024
|
A17.1-2016 : Elevators
|
1.15 - sign and operating device symbols
|
2.26.12
|
|
|
Install a star on the main floor door jamb.
|
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
3.26.10
|
x
|
|
The auxiliary power lowering operation shall be functional.
|
10/17/2024
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The in car telephone shall be operational. Note: The phone was tested 5 times. Each time it dialed out but wasn't answered.
|
10/17/2024
|
A17.1-2016 : Elevators
|
1.7 - Car door or gate
|
3.11
|
|
|
Adjust the gap on the front cab door to not exceed 3/8".
|
|
A17.1-2016 : Elevators
|
1.9 - Power closing of doors or gates
|
2.13.4.2.2
|
|
|
Complete the door time labels.
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing
|
|
|
This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test.
|
8/26/2022
|
A17.1-2016 : Elevators
|
2.1 - Access to machine space
|
2.7.3.1
|
|
|
A permanent and unobstructed means of access to the elevator machine room shall be provided. Note: During the test, the machine room door was partially blocked. This door shall not be blocked.
|
|
A17.1-2016 : Elevators
|
2.1 - Access to machine space
|
2.7.3.4
|
|
|
The machine room shall have a self-closing and self-locking door and shall be operable from the interior space without the use of a key.
|
|
A17.1-2016 : Elevators
|
2.10 - Numbering of Elevators, Machines, Controllers, and Disconnect Switches
|
2.29.1
|
|
|
Install the elevator number on the main floor door jamb.
|
|
A17.1-2016 : Elevators
|
2.14 - Code data plate
|
8.6.1.5
|
|
|
A code data plate is required.
|
|
A17.1-2016 : Elevators
|
2.6 - Ventilation
|
2.7.9.2
|
|
|
Install an A/C system in the machine room.
|
|
A17.1-2016 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
|
|
An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door.
|
|
A17.1-2016 : Elevators
|
3.10 - Hoistway construction
|
2.1
|
|
|
Seal the joint between the hoistway block walls and the building brick walls.
|
|
A17.1-2016 : Elevators
|
3.10 - Hoistway construction
|
2.1
|
|
|
Seal all penetrations in the hoistway and machine room.
|
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2.5 Sump Pump Required/Capacity (Re-Inspect)
|
x
|
|
Verify the discharge capacity of the sump pump.
|
7/13/2023
|
conversion
|
conversion
|
n/a
|
|
|
4"x 4" electrical junction box in machine room is missing its cover. Said junction box shall have a cover installed.
|
9/4/2019
|
A17.1-2016 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
|