Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars No No Clean the car top. 8/28/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts No No The standby power selector switch and light shall be removed or marked "for future use" - the building is not equipped with emergency power for the elevators. 8/28/2026
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log No No A record of findings for firefighters' service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be kept on site. 8/28/2026
A17.1-1996 : Elevators 1.17 - Standby power operation 1001.2(a)(17) Yes No Emergency power shall be tested. 9/30/2021
A17.1-1996 : Elevators 1.18 - Restricted opening of car or hoistway doors 1001.2(a)(18) Yes No Make car door restrictor operational. 6/6/2019
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Two-way communication device is not functioning and needs repair. 8/28/2026
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Emergency phone shall be tested and shall operate with and without main power. 9/19/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Fire service shall be tested to complete the annual inspection. 9/19/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Fire service operation shall be tested as required. 8/12/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Need to simulate the fire alarm initiating devices for phase 1 recall. 9/30/2021
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Category 5 testing shall be completed. The following testing items remain: Counterweight buffer shall be tested at contract speed, 125% brake test, car safeties shall be set at contract speed with full load, and car buffer shall be tested with full load at contract speed. 9/13/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Fire Service Phase 1 and 2 shall be tested to complete CAT5.
A17.1-1996 : Elevators 2.3 - Lighting and receptacles 101.5a Lighting No No Lighting in machine room shall be not less than 10fc at floor level. Recommend adding light fixture over controller as personnel are having a hard time seeing equipment. 8/28/2026
A17.1-1996 : Elevators 2.4 - Machine space 100.3d No No Lighting in machine room shall be not less than 10fc at floor level. Recommend adding light fixture over controller as personnel are having a hard time seeing equipment.
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No MCP, including PM records, not being retained properly. MCP/Records shall be kept in the Machine Room for 5 years.
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No Provide on-site maintenance documents (MCP). 8/28/2026
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Rescue plan is missing. (This item is for notification purposes for future violation in 2022) 8/28/2026
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No A record of findings for firefighters' service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be kept on site. 8/28/2026
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No A maintenance control program shall be provided in machine room. 8/28/2026
A17.1-1996 : Elevators 2.5 - Housekeeping 1206.2c (Clean Car Tops) No No Cartop shall be kept free of excess debris/dirt/lint.
A17.1-1996 : Elevators 3.17 - Door and gate equipment 110 No No Hoistway doors shall be self-closing
A17.1-1996 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 107.1b Yes No Counterweight runby does not meet Code Minimum of 6".
A17.1-1996 : Elevators 5.6 - Governor-rope tension devices 1001.2(e)(7) No No Governor Tail Sheave only has about 1" of travel remaining.
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 211.7 Firefighter' Service Operating Procedures No No MCP - Fire Service must be tested and properly documented monthly on an on-site Log Sheet
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Current State Operating Permit shall be displayed in the Equipment Room in a non-combustible frame.
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 8/28/2026
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 8/28/2026
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Display a current state operating certificate in the elevator machine room. 8/28/2026
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Display current state operating certificate. 8/28/2026